Fire Safety (Building and Pipeline Fire Safety) Regulation 4(4)

THE SCHEDULE

MINOR ALTERATIONS OR

ADDITIONS NOT REQUIRING APPROVAL OF PLANS

1

The following minor alterations or additions that are within or in relation to an individual unit in a building and that satisfy paragraphs 4, 5, 6 and 7, where applicable:

  1. partition works arising from change of use to ancillary usage as a pantry, a toilet, a store room of not more than 20 square metres, an ancillary office or other similar use, without increase in occupancy load;

  2. replacement or addition of any electromechanical locking device to any non-fire rated exit or exit access door, including a unit door;

  3. replacement, relocation or addition of any roller shutter, swing or sliding door for any nonfire rated exit or exit access door, including a unit door;

  4. replacement, relocation or addition of any raised floor with a depth of not more than 150 millimetres that does not result in a total area of raised floor within the individual unit exceeding 200 square metres;

  5. replacement, relocation or addition of any false ceiling;

  6. replacement, relocation or addition of any kitchen fire suppression system;

  7. replacement, relocation or addition of any flammable material cabinet where the maximum allowable quantity is limited to 500 litres per control unit;

  8. replacement or relocation of any pipeline that conveys any flammable or combustible liquid or gas;

  9. relocation, replacement or addition of any fire alarm subpanel serving an individual unit;

  10. any internal partition works within an individual unit.

2

The following minor alterations or additions that are to the interior of a building other than an excluded building and that satisfy paragraphs 4, 5, 6 and 7, where applicable:

  1. replacement, relocation or addition of any portable fire extinguisher, hose reel, exit sign or emergency lighting;

  2. replacement, relocation or addition of any fire alarm bell, manual call point, detector and strobe light;

  3. replacement, relocation or addition of any one-way emergency voice communication component;

  4. replacement or relocation of any fire alarm panel;

  5. replacement of any dedicated fire hose reel pump or water tank;

  6. replacement, relocation or addition of any sprinkler;

  7. replacement, relocation, addition or extension of any air-conditioning or mechanical ventilation duct and fan that is not fire-rated or part of the fire safety system.

3

The following alterations or additions that are outside of a building and that satisfy paragraphs 4, 5, 6 and 7, where applicable:

  1. construction of any open-sided linkway that is not more than 5 metres in width, and not used for commercial activities;

  2. construction of any standalone pedestrian underpass that is not more than 5 metres in width, and not used for commercial activities;

  3. construction of any overhead bridge (whether or not enclosed) that is not more than 5 metres in width, and not used for commercial activities;

  4. installation of any solar panel at the roof of a building only;

  5. construction of any outdoor display area.

4

Any minor alterations or additions must not —

  1. affect the fire resistance of any element of structure;

  2. affect any, or involve the erection or installation of any form of, fire compartmentation (including fire resisting walls or doors in the building);

  3. pose additional fire hazard to the building;

  4. affect the wet or dry riser or landing valve;

  5. involve change of use except ancillary usage as a pantry, a toilet, a store room of not more than 20 square metres, an ancillary office or other similar use, without any increase in occupancy load;

  6. involve an increase in floor area; or

  7. involve conservation projects.

5

Any partition works or internal partition works to an individual unit other than a shop or an office must not result in a room with a floor area exceeding 200 square metres.

6

Any minor alterations or additions to any air-conditioning or mechanical ventilation system must not involve the replacement or relocation of any duct or fan in relation to any of the following:

  1. exit staircases and internal exit passageways;

  2. pressurisation of internal corridors in hotels and premises used for healthcare purposes;

  3. smoke-free lobbies or fire lift lobbies;

  4. fire pump rooms, generator rooms, Fire Command Centre or rooms involving storage or use of flammable and explosive substances;

  5. engineered smoke control systems;

  6. smoke purging systems.

7

Any minor alterations or additions to a fire protection system or fire alarm system must not —

  1. involve the replacement, relocation or addition of any sprinkler classified under OH3S or high hazard;

  2. involve the replacement, relocation or addition of more than 9 sprinkler heads; or

  3. involve the replacement, relocation or addition of sprinklers or detectors along any common area of a building with sleeping risks such as hospitals, hotels and worker dormitories.

8

In this Schedule —

“excluded building” means any building —

  1. where there can be a large congregation of the general public, such as religious premises;

  2. used for childcare or healthcare purposes, where the occupants have impaired mobility or are vulnerable in the event of a fire emergency; or

  3. with high fire loads or hazards;

“individual unit”, in relation to a building, means —

  1. any room designated as a shop or an office in an approved building plan under a temporary fire permit or fire safety certificate; or

  2. any room with a floor area of not more than 200 square metres in an approved building plan under a temporary fire permit or fire safety certificate.

    [S 769/2020 wef 14/09/2020]