Explanations & Illustrations
The requirements for provision of emergency lighting for corridors and lobbies in respect of:
min. level of luminance;
spacing of luminaires; and
c. delay (1 second) for the emergency lighting are similar to C.8.1.1.
Corridors and lobbies, including routes of escape, smoke-stop lobbies, common lobbies, are required to have min. 0.5 lux, measured at the floor, for minimum duration of 1 hour, notwithstanding that residents may be presumed to be familiar with exit facilities by reason of regular usage of such facilities.
The emergency lighting system shall be so arranged to provide the required illumination by means of standby generator set upon failure of public utility supply. The changeover from one energy source to another shall not incur a delay of more than 15 secs. This is considered a reasonable short time for the generating plant to start. However, where battery packs are used for emergency power, they must be the type that will automatically be kept charged and be able to perform for a minimum duration of 1 hour.