This document is adapted from an official source and formatted for consistency. While Builtsearch aims to keep it accurate and up to date, please refer to the original source for the most reliable and current information.

Document Version: 2023

Fire Code

7

Mechanical Ventilation & Smoke Control Systems

7.1

Air-Conditioning and Mechanical Ventilation Systems

7.1.1

General

Where an air-conditioning system is provided in lieu of a mechanical ventilation system for emergencies, all the requirements specified in this Code for mechanical ventilation systems shall apply to the air-conditioning system.

Explanations & Illustrations

The term “air conditioning” has been defined by the American Society of Heating, Refrigerating, and Air Conditioning Engineers as:

“Air conditioning is the process of treating air so as to control simultaneously its temperature, humidity, cleanliness and distribution to meet the requirements of the conditioned space”.

The use of air-conditioning and mechanical ventilation systems will invariably, except for self-contained split units, involve some use of pipe works and ducts for air distribution and removal.

The use of ducts present the inherent possibility of spreading fire, heat, gases and smoke throughout the building or the floors/areas served.

Where air-conditioning system is designed to operate during fire emergency, it is to be emphasized that the system shall comply with all the relevant requirements for the mechanical ventilation system in this Code.

7.1.2

Construction of ductwork

Ducts for air-conditioning and mechanical ventilation systems shall be constructed in compliance with all of the following requirements:

  1. Materials

    Air-conditioning or other ventilation ducts, including framing thereof, shall be constructed of steel, aluminium, glass fibre batt or mineral wool batt or other approved materials. 

  2. Support 

    Air-conditioning or other ventilation ducts shall be adequately supported. 

  3. Duct linings & coverings

    Duct covering and lining shall be non-combustible. However, if it is necessary to use combustible material, it shall:

    1. when tested in accordance with methods specified in this Code, have a surface flame spread rating of not lower than Class 1, except in areas of a building where Class 0 flame spreading rating is required for the ceiling construction under this Code, a Class 0 rating for the covering and lining materials shall instead be required;

    2. when involved in fire, generate a minimum amount of smoke and toxic gases; and

    3. be at least 1m away from a fire damper.

  4. Flexible joints and connections

    1. Flexible connections at the ends of ventilation ductwork connecting terminal units, extract units and ventilation grilles shall not exceed 4m.

    2. Flexible joints, which are normally provided to prevent and/or allow for thermal movements in the duct system, shall not exceed 250mm in length.

    3. Flexible joints shall be made of material classified as ‘not easily ignitable’ when tested under BS 476: Part 5.

  5. Duct enclosure

    Enclosure of ducts shall comply with the requirements in Cl.3.8.9a..

Explanations & Illustrations

Clause 7.1.2 : Construction of ductwork

Figure 7.1.2
Figure 7.1.2

Insulation material/barrier lining and adhesives shall have minimum Class 1 flame spread rating. Where ceiling construction requires Class 0, covering and lining insulation material shall also be Class 0. Where combustible material is used for the insulation of the duct, it shall be kept at least 1000mm away from a fire damper in order to prevent premature closing of the damper arising from a fire from the combustible insulation material. For flexible joints and connections which are combustible, there is a need to limit the length of the joints and connection to max. 250mm and 4m respectively.

Clause 7.1.2e. : Construction of ductwork

A protected shaft used for the enclosure of services shall comply with the following:

  1. The protecting structure for protected shaft containing kitchen exhaust duct and mechanical ventilation ducts serving areas specified in Cl.5.2.1g.(1)(a), (b), (c), (i) and Cl.5.2.1h. which passes through one or more floors shall be masonry. Such shaft shall be completely compartmented from the rest of the shaft space containing other ducts or any other services installations.

  2. For protected shaft containing ducts serving other areas which passes through two or more floors shall be constructed of fire-rated material.

  1. Ductwork through smoke-free or fire lift lobbies

    Ventilation ducts should not pass through smoke-free or fire lift lobbies. Where unavoidable, the part of the ventilation duct within the lobby shall be enclosed in masonry construction with fire resistance rating at least equal to that of the elements of structure. If other forms of fire resisting construction are used, a fire damper shall be fitted where the duct penetrates the lobby enclosure.

Explanations & Illustrations

Clause 7.1.2f. : Construction of ductwork

Section Figure 7.1.2f. - 1
Section
Figure 7.1.2f. - 1

In addition to providing fire-rated enclosure to the duct within the lobby, fire damper is fitted where the duct penetrates the lobby enclosure. Should a fire penetrates the fire damper, it will still be contained within the duct.

Section Figure 7.1.2f. - 2
Section
Figure 7.1.2f. - 2

The omission of fire damper to the duct where it penetrates the lobby enclosure is acceptable if a masonry slab is constructed below the duct to act as compartment ceiling. The masonry slab over the lobby completes the compartmentation making the lobby a safe area.

Figure 7.1.2f. - 3 : Routing of ventilation ducts directly from AHU room to office space
Figure 7.1.2f. - 3 : Routing of ventilation ducts directly from AHU room to office space

With proper pre-planning, ventilation ducts are routed directly from the AHU rooms to occupancy areas, thus avoiding the routing through the protected lobby.

Figure 7.1.2f. - 4 : Routing of ventilation ducts along protected lobby
Figure 7.1.2f. - 4 : Routing of ventilation ducts along protected lobby

Ventilation ducts are routed along the smoke-stop lobby to serve office 2 & 3. Routing the ventilation ducts through the fire lift or smoke-stop lobbies should be avoided. “Unavoidable situations” where ventilation ducts were routed through the fire lift or smoke-stop lobbies referred to existing building where physical constraints existed making it difficult to route the ventilation duct through other spaces other than the lobby area.

  1. Ductwork through separating walls

    No air-conditioning or ventilation duct shall penetrate separating walls.

Explanations & Illustrations

Clause 7.1.2g. : Construction of ductwork

Axonometric section Figure 7.1.2g. - 1
Axonometric section
Figure 7.1.2g. - 1

A separating wall is a division wall that separate adjoining buildings of different ownership. Ducts are prohibited to penetrate separating wall to prevent fire spread from one building to another.

2nd storey floor plan Figure 7.1.2g. - 2
2nd storey floor plan
Figure 7.1.2g. - 2

In terrace shophouses, there should be no sharing of air-con ducts.

  1. Fire-rated duct

    1. Where proprietary fire-rated materials are used to construct the fire-rated duct, the fire rating of the fire-rated duct shall have the same period of fire resistance as the wall or floor it penetrates.

    2. Proprietary fire-rated duct shall be tested to BS 476 Part 24 or equivalent and its usage be approved by the SCDF.

    3. Running of non-fire-rated duct and/ or other building services above the proprietary fire-rated duct should be avoided. When unavoidable due to physical constraints, the supports to such non-fire-rated duct and/ or other building services running above the proprietary fire-rated duct shall be strengthened, such that the tensile stress generated on the supports shall not exceed 10N/mm2. The non-fire-rated duct and/ or building services shall also be adequately protected to prevent collapse in a fire which will otherwise affect the stability of the proprietary fire-rated duct below.

    4. Fans forming part of a fire-rated duct shall also be enclosed in the same fire-rated enclosure.

  2. Control panel

    1. The location and placement of control panels serving engineered smoke control and smoke purging systems shall be located within a common space such that the panels are clearly visible and readily accessible for operation and maintenance. Control panel shall be mounted at a height not less than 1.5m or not more than 1.8m from the finished floor level.

    2. For control panels serving smoke purging systems, it shall be located at least 1.5m away from fire hazards e.g. control panels for smoke purging system in carparks sited away from vehicle parking lots. Alternatively, the control panel shall be protected with at least 1-hr fire resisting rating enclosure.

Explanations & Illustrations

Clause 7.1.2h.(3) : Construction of ductwork

Section Figure 7.1.2h.(3)
Section
Figure 7.1.2h.(3)

Rationale

Clause 7.1.2i

The control panel serving the fans of smoke control systems are crucial and should not be located within any smoke layer to ensure that the integrity of the smoke control system is not compromised in an fire emergency. The exhaust systems would not be operable in the event of failure of the control panels.

7.1.3

Pipework

Insulation for pipework associated with the air-conditioning and mechanical ventilation systems shall comply with the following requirements:

  1. Flame spread rating

    Insulation material for pipework, together with vapour barrier lining and adhesives shall, when tested in accordance with the methods specified in this Code, have a surface flame spread of not lower than Class 1. However, in areas of buildings where Class 0 flame spread is required for the ceiling construction under this Code, a Class 0 rating for the insulation material shall be required.

  2. Plastic and foam rubber insulation

    Notwithstanding the requirements of Cl.7.1.3a., the use of plastic and foam rubber insulation materials of a lower classification is permitted if:

    1. it is of the self-extinguishing type; and

    2. the insulation is covered by or encased in a metal sheath or hybrid plaster or other non-combustible cladding material,

    provided that any opening in the element of structure or other part of a building penetrated by the pipework shall be effectively fire-stopped by replacement of the insulation material at the junction of penetration with fire resistant material having equal fire resistance rating. A fire-rated proprietary pipework system can be used if it is tested in the manner acceptable to the SCDF.

Explanations & Illustrations

Clause 7.1.3 : Construction of ductwork

Section Figure 7.1.3 - 1 : Metal pipes with combustible insulation
Section
Figure 7.1.3 - 1 : Metal pipes with combustible insulation
Section Figure 7.1.3 - 2 : Metal pipes with non-combustible insulation
Section
Figure 7.1.3 - 2 : Metal pipes with non-combustible insulation
Section Figure 7.1.3 - 3 : : Plastic pipes with non-combustible insulation
Section
Figure 7.1.3 - 3 : : Plastic pipes with non-combustible insulation

Minimum Class 1 for insulation material/barrier lining and adhesives. Where ceiling construction requires Class 0, insulation material shall also be class 0. However, the use of 10mm to 15mm max. pipe works for split unit system would be considered as acceptable.

The use of fire collar shall be appropriate for the diameter of the PVC/UPVC pipe and shall be duly secured to the surface of the wall or floor with steel anchor bolts.

7.1.4

Air plenum

A concealed space between the ceiling and floor above it, ceiling and roof, or raised floor and structural floor of a building can be used as a plenum provided:

  1. The concealed space contains only:

    1. mineral insulated metal sheathed cable, aluminium sheathed cable, copper sheathed cable, rigid metal conduit, enclosed metal trunking, flexible metal conduit, liquid tight flexible metal conduit in lengths not more than 2m, or metal-cladded cables;

    2. electric equipment that is permitted within the concealed spaces of such structures, if the wiring materials, including fixtures, are suitable for the expected ambient temperature to which they will be subjected;

    3. other ventilation ducts complying with Cl.7.1.2a. to d.;

    4. communication cables for computers, television, telephone and inter-communication systems;

    5. fire protection installations; and

    6. pipes of non-combustible material conveying non-flammable liquids.

  2. The supports for the ceiling membrane are of non-combustible material.

  3. Exception

    Low-smoke and low-flame plenum rated PVC cables conforming to NFPA 262 can be run exposed in plenum, provided that:

    1. the plenum space is protected by a sprinkler system or gaseous total flooding system; and

    2. a FCU or AHU using a plenum for air return and serving more than one room, is installed with smoke detector(s) at the return air plenum space to shut down the FCU/ AHU upon detection of smoke.

Explanations & Illustrations

Clause 7.1.4 : Air plenum

Section Figure 7.1.4 - 1 : Concealed ceiling space
Section
Figure 7.1.4 - 1 : Concealed ceiling space
Section Figure 7.1.4 - 2 : Concealed space below raised floor
Section
Figure 7.1.4 - 2 : Concealed space below raised floor

The main reasons for imposing additional fire safety requirements are that a fire occurring in the concealed space would be difficult to detect and that smoke and heat would quickly spread beyond the concealed space.

Sprinkler system is usually not provided in the concealed space, hence, all the supports for the raised floor or ceiling membrane shall be of non-combustible material. Ceiling plenum provides the means for transferring heat, smoke and fire, hence there should be a very strict control on the amount of combustible materials in it.

Section Figure 7.1.4 - 3 : Return air in ceiling space
Section
Figure 7.1.4 - 3 : Return air in ceiling space
Section Figure 7.1.4 - 4 : Return air plenum in concealed space below raised floor
Section
Figure 7.1.4 - 4 : Return air plenum in concealed space below raised floor

A fire occurring in the concealed space would be difficult to detect. The smoke and heat could quickly spread beyond the origin of fire in the concealed space.

To restrict the unseen spread of smoke and heat in concealed spaces, additional fire safety requirements are imposed under Cl.7.1.4a. and  Cl.7.1.4b..

Section Figure 7.1.4 - 5
Section
Figure 7.1.4 - 5
Section Figure 7.1.4 - 6
Section
Figure 7.1.4 - 6
Figure 7.1.4 - 7
Figure 7.1.4 - 7
Section A-A Figure 7.1.4 - 8
Section A-A
Figure 7.1.4 - 8

Low-flame and low-smoke plenum rated PVC cables conforming to NFPA 262 are permitted to be run exposed in plenum, provided that the plenum shall be protected by sprinkler system or gaseous total flooding system.

In the case of Fan Coil Unit (FCU) or Air Handling Unit (AHU) using plenum for air return and serving more than one rooms, it shall be provided with smoke detection at the return air plenum. This is to address smoke detection within the air plenum space.

7.1.5

Fire Dampers

Any fire damper shall have a fire resisting rating of not less than that required for the compartment wall or compartment floor through which the relevant section of the ventilation duct passes. Fire dampers shall be of the type approved by the SCDF and constructed in accordance with the requirements in SS 333.

  1. Provision of fire dampers

    Ventilation ducts which pass directly through a compartment wall or compartment floor shall comply with the following:

    1. where the ventilation duct does not form a protected shaft or is not contained within a protecting structure, the duct shall be fitted with a fire damper where it passes through the compartment wall or compartment floor; and

    2. where the ventilation duct forms a protected shaft or is contained within a protecting structure, the duct shall be fitted with fire dampers at the shaft inlets and outlets.

Explanations & Illustrations

Clause 7.1.5a. : Fire dampers

Section Figure 7.1.5a. - 1
Section
Figure 7.1.5a. - 1

Exposed ventilation duct is not fire-rated. Fire damper is provided where it passes through the compartment floor or wall to prevent fire spread from compartment to compartment via the duct.

Section Figure 7.1.5a. - 2
Section
Figure 7.1.5a. - 2

To prevent fire spread from compartment to compartment via the duct, fire damper shall be provided at the inlets to the exhaust air shaft and outlets from supply air shaft.

The dampers shall be properly secured to the protecting structure or protected shaft to prevent any displacement. The method of installation shall follow the type tests shown in the test report issued by testing laboratory.

Fire dampers are provided to inlets of exhaust air shafts and outlets of supply air shaft

Figure 7.1.5a. - 3
Figure 7.1.5a. - 3
  1. Installation of fire dampers

    1. Fire dampers shall be installed so that the casing completely penetrates through the compartment wall or floor, and the casing shall be retained, either:

      1. on both sides by means of flanges in such a manner that it can expand under fire conditions without distorting the blades in the closed position, or

      2. on the accessible side by means of one flange only, which can be fixed to the damper and to the wall through slotted holes to allow for expansion.

    2. Flanges shall be butted against the face of the compartment wall or floor and fixed to the damper casing.

    3. Ductwork connected to the damper shall be attached in such a manner as to ensure that the damper remains securely in position and is fully functional in the event of damage of ductwork.

    4. The clearance between the damper body and the sides of the penetration shall not be less than that of the tested prototype and be not greater than half the width of the angled section of the collar.

    5. The space between the damper body and the opening in the wall or floor shall be fire-stopped.

    6. Vertically positioned fire dampers shall be installed in such a manner that the direction of air flow assists in the closure of the damper.

    7. Connections to fire dampers

      The distance between the plane through a closed fire damper and ducting, flexible connections, duct coverings, internal linings and the like, shall be

      1. not less than 1m when such parts are made of materials with fusing temperatures less than 1000oC;

      2. not less than three times the diagonal or diameter of the damper; and

      3. not less than 2m when such parts are made of materials that are combustible, except for vapour barrier to provide thermal insulation.

    8. Fire damper inspection access doors

      Each fire damper installation shall be provided with an inspection access door in the ventilation duct, either upstream or downstream, as appropriate. The access door dimension shall measure 450mm (length) X 450mm (width); for smaller ducts, the door width dimension can be reduced to the width or depth of the duct. Access doors shall be hinged and fitted with sash locks, and be constructed of minimum 1.25mm suitably braced sheet steel. Openings in ducts shall be stiffened by a sheet steel frame.

  2. Prohibition of fire dampers

    Fire dampers shall not be fitted in any of the following locations:

    1. openings in walls of a smoke extract shaft, or a return air shaft which also serves as a smoke extract shaft, or

    2. openings in walls of a protected shaft when the openings have a kitchen exhaust duct passing through it, or

    3. opening in walls of a protected shaft when the openings have a fume hood exhaust duct passing through it, or

    4. anywhere in an air pressurising system, or

    5. in locations explicitly prohibited in this Code.

  3. Standards

    Where a fire damper is required by this Code to be installed in an air- conditioning and mechanical ventilation system, its type, details of installation, connection of accessories, inspection door, etc., shall be in accordance with SS 333.

Explanations & Illustrations

Clause 7.1.5c. : Fire dampers

Figure 7.1.5c. : Car park smoke purging system
Figure 7.1.5c. : Car park smoke purging system

Fire dampers shall not be fitted in any of the supply air shaft or extract air shaft. The smoke purging system would fail as the fire dampers when in closed position would prevent movement of air within the shaft.

Fire dampers shall not be provided in the following locations:

  1. openings in wall of a protected shaft serving kitchen exhaust;

  2. anywhere in the supply duct work of air pressurising system to exit staircase; and

  3. anywhere in the supply and exhaust ducts serving fire pump room, generator room, FCC and flammable store.

7.1.6

Fire resisting floor ceiling and roof ceiling

  1. The space above a suspended ceiling which forms part of a fire-rated floor ceiling or roof ceiling construction shall not contain ducting, unless said ducting was incorporated in a prototype that qualified for the required fire resistance rating, in which case the ducting shall be identical to that incorporated in the tested prototype.

  2. Openings in the ceiling, including openings to enable the ceiling to be used as a plenum, shall be protected by fire dampers identical to those used in the tested prototype. Such openings in the ceiling shall be so arranged that:

    1. no opening is greater in area than that in the corresponding prototype test panel;

    2. the aggregate area of the openings per unit ceiling area does not exceed that of the prototype test panel; and

    3. the proximity of any opening to any structural member is not less than that in the prototype test panel.

Explanations & Illustrations

Clause 7.1.6a. : Fire resisting floor ceiling & roof ceiling

Figure 7.1.6a. : Ducting above fire-rated ceiling or roof ceiling construction
Figure 7.1.6a. : Ducting above fire-rated ceiling or roof ceiling construction

Mechanical ventilation ducts are not permitted to be located in the concealed space of fire-rated floor ceiling or roof ceiling assembly, unless such ducts are included in the prototype that was tested for the required fire resistance rating. The type of ducting within such ceiling or roof spaces as well as details of openings in such ceiling shall be identical to that incorporated in the tested prototype.

Clause 7.1.6b. : Fire resisting floor ceiling & roof ceiling

Figure 7.1.6b.
Figure 7.1.6b.
  1. Area of each opening (A & B) shall not be greater or larger than that in the prototype test panel.

  2. Total area of openings (A & B) for ceiling to each compartment shall not be greater than that of the prototype test panel.

  3. The opening (A & B) can be relocated within the ceiling area provided the proximity to structural member, e.g. column, beams and structural walls is not less than that in the prototype test panel.

7.1.7

Locations of intakes and return air openings

  1. Openings for the intakes of outdoor air to all air handling systems, mechanical ventilation systems, pressurisation systems of exit staircases and internal corridors, and smoke control systems shall be no less than 5m from any exhaust discharge openings.

  2. All return air openings and outdoor air intakes shall be located and arranged such that sources of ignition, such as lighted matches and cigarette butts, which accidentally enter the openings and intakes cannot be deposited onto the filter media.

7.1.8

Air handling unit (AHU) room

  1. Air plenums

    Air handling systems shall not use protected shafts of exits, smoke-free lobbies, including its concealed space for supply, exhaust or return air plenums.

  2. Compartmentation

    1. Where the air handling equipment serves more than one compartment, fire dampers shall be provided in air ducts at penetrations through the compartment walls and floors to comply with the requirements in Cl.7.1.5.

    2. Where AHU rooms are vertically stacked, each AHU room shall be separated by a compartment floor at every level.

  3. Smoke detectors

    1. Smoke detectors of approved type shall be incorporated in the return air stream immediately adjacent to:

      1. AHUs serving more than one storey or compartment, or

      2. a single AHU in excess of 15000m³/h.

    2. The function of smoke detectors, where required by this Code, is to initiate action to shut down the AHU automatically when the smoke density in the return air system has become unacceptable for recycling.

  4. Stop switch

    Where the AHUs in a building are not centrally controlled, each AHU exceeding 8500m³/h shall be provided with a manual stop switch to facilitate quick shutting down of the fan in the case of fire. For ease of access, this switch shall be located on the wall next to the door opening of the air handling equipment room.

Explanations & Illustrations

Clause 7.1.8b.(1) : Air handling unit room

Figure 7.1.8b.(1)
Figure 7.1.8b.(1)

Where the AHU serves more than one compartment, fire dampers shall be provided in air ducts at penetrations through the compartment walls and floors.

Clause 7.1.8b.(2) : Air handling unit room

Figure 7.1.8b.(2)
Figure 7.1.8b.(2)
  1. Some practice of using fire-rated ceiling at the underside of the metal platform for vertically stacked AHU rooms which will likely deteriorate over time due to moisture or dampers, is no longer permitted.

  2. Vertically stacked AHU rooms shall be separated by a compartment floor at every level.

Rationale

Clause 7.1.8b

Rooms having no usage other than housing air handling equipment or package units, and their associated electrical controls are typically not regarded as areas of high risk and therefore compartmentation is not required. However, fire dampers shall be provided within the air ducts of the air handling equipment where they penetrate through compartments to prevent fire spread.

7.1.9

Ventilation system for exits

  1. Air plenums

    Protected shaft of exits, smoke-free lobbies, including their concealed spaces shall not be used for supply, exhaust or return air plenum of air handling systems.

  2. Exit staircase and internal exit passageway

    A mechanical ventilation system for each exit staircase and internal exit passageway, if provided, shall be an independent system of supply mode only exclusive to the particular staircase and internal exit passageway, and it shall comply with all of the following requirements:

    1. Supply air for the system shall be drawn directly from the external space, with intake point not less than 5m from any exhaust discharge openings.

    2. For exit staircase serving more than four storeys, supply air shall be conveyed via a vertical duct extending throughout the staircase height and discharging through outlets distributed at alternate floors.

    3. Where the supply air duct serving the exit staircase has to penetrate the staircase enclosure, the portion of the duct where it traverses outside the staircase shall be enclosed in masonry construction or drywall complying with Cl.3.8.7b. of at least the same fire resistance as the elements of structure, and it shall not be fitted with fire dampers.

    4. The ventilation system shall be of supply mode only, and of not less than 4 air changes per hour.

    5. The mechanical ventilation system shall be automatically activated by the building fire alarm system. In addition, a remote manual start-stop switch shall be made available to firefighters at the FCC, or, where there is no FCC, at the fire alarm panel.

    6. Visual indication of the operational status of the mechanical ventilation system shall be provided.

Explanations & Illustrations

Clause 7.1.9a. : Ventilation system for exits

Section Figure 7.1.9a..
Section
Figure 7.1.9a..

The protection of these spaces as means of escape is important. They must not be used as air plenum by other systems.

Clause 7.1.9b.(2) : Ventilation system for exits

Section Figure 7.1.9b.(2).: Mechanical ventilation to exit staircase and internal exit passageway
Section
Figure 7.1.9b.(2).: Mechanical ventilation to exit staircase and internal exit passageway

There is a need to separate supply air fan from the exhaust louvres by at least 5m measured from the edge of the exhaust louvres housing. This is to prevent the possibility of smoke being drawn into the supply air shaft. The exhaust louvres (outlet) shall not face directly to any inlet of air supply.

For maintaining uniformity of air distribution in the staircase it would be desirable to place the supply air outlet at every floor level, but should not be more than alternate floors. The supply air system to the staircase shall be an independent system as it is expected to operate during emergency to provide smoke free environment to serve occupants evacuating in the staircase.

Clause 7.1.9b.(3) : Ventilation system for exits

Section Figure 7.1.9b.(3).
Section
Figure 7.1.9b.(3).

The supply air duct is considered as part of the exit staircase, as such that part of the duct which traverses outside shall be protected.

As exit staircase is the means of escape, protecting it with masonry or equivalent would ensure the durability of the shaft during a fire situation.

As far as possible, the supply air duct should be located within the protected shaft, unless it is unavoidable.

7.1.10

Ventilation system for smoke-free lobby and fire lift lobby

  1. The ventilation system shall be of supply mode only of not less than 10 air changes per hour.

  2. Supply air shall be drawn directly from the external space with intake point not less than 5m from any exhaust discharge or openings for natural ventilation.

  3. Any part of the supply duct running outside the smoke-free or fire lift lobby which it serves shall either be enclosed or constructed to give a 1-hr fire resistance rating. The SCDF may, at its discretion, require a higher fire resistance rating if the duct passes through an area of high fire risk.

  4. The mechanical ventilation system shall be automatically activated by the building fire alarm system. In addition, a remote manual start-stop switch shall be made available to firefighters at the FCC, or, where there is no FCC, at the main fire alarm panel.

  5. Visual indication of the operational status of the mechanical ventilation system shall be provided.

  6. Where air conditioning is required for daily operations, this can be provided via supply and return air duct from the FCU/ AHU outside of the smoke-free/ fire lift lobby. Fire dampers shall be provided in the supply and return air ducts at penetrations through the compartment walls and/or floors. The ducts shall be fire-rated if it forms part of the other services passing through the smoke-free/ fire lift lobbies and/or the duct insulations are not of non-combustible type.

Explanations & Illustrations

Section Figure 7.1.10 : Mechanical ventilation of smoke-stop/fire lift lobbies
Section
Figure 7.1.10 : Mechanical ventilation of smoke-stop/fire lift lobbies

The above figure shows that the supply air duct to the smoke-stop lobbies or fire fighting lobbies is provided with fire damper where it penetrates the compartment wall of the lobby. This is to ensure that the floor to floor compartmentation is maintained.

The portion of the duct which traverse outside the protected shaft is enclosed in fire rated construction e.g. fire-rated boards comply with Cl.3.8.9a. or  Cl.3.8.7b.. The purposes of locating the manual start/stop switch with visual indication at the FCC, or at the main fire indicating board (FIB) where there is no FCC are:

  1. to allow firefighting personnel to shut down the supply air system temporarily in the event that smoke is being drawn into the lobby through the outdoor air intake; and

  2. to allow firefighting personnel to activate the supply air system should the fire alarm system fail to automatically activate the supply air system.

7.1.11

Ventilation system for fire pump room and generator room

Where mechanical ventilation is installed to provide a smoke-free environment for the room housing the fire pump or emergency generator, such systems shall be independent of each other and of any other system serving other parts of the building, and shall comply with all of the following requirements:

  1. Supply air shall be drawn directly from the external space and its intake point shall not be less than 5m from any exhaust discharge openings. Exhaust discharge shall also be direct to the external space.

  2. Where the corresponding ducts run outside the room they shall either be enclosed in a structure or be constructed to give at least the same fire rating as the room which they serve, or that of the room through which they traverse, whichever is higher. The rating shall apply to fire exposure from both interior and exterior of the duct or structure. Where the duct risers are required to be enclosed in a protected shaft constructed of masonry or drywall complying with Cl.3.8.7b., they shall be compartmented from the rest of the shaft space containing other ducts or service installations.

  3. No fire damper shall be fitted in either supply or exhaust duct required under this clause.

  4. A duct serving areas other than rooms housing equipment stated in this clause shall not pass through such rooms.

Explanations & Illustrations

Clause 7.1.11a. : Ventilation system for engine-driven fire pump room and generator room

Section Figure 7.1.11a.
Section
Figure 7.1.11a.

The 5m clearance between supply and exhaust units refers to the horizontal distance. This is to prevent the recycling of exhaust air back into the building.

Clause 7.1.11b. : Ventilation system for engine-driven fire pump room and generator room

Section Figure 7.1.11b.
Section
Figure 7.1.11b.

The above figure shows that the ducts that run outside the protected shaft are enclosed in a structure or be constructed to give the necessary fire resistance rating. However, for the riser ducts which pass through one or more floors they are required to be enclosed in masonry shaft or drywall as required under Cl.3.8.9a.. This is to ensure that the riser ducts are properly protected within a shaft. The enclosure would ensure the integrity and stability of the riser ducts which pass floor to floor.

The provision of fire damper in the supply or exhaust duct is not allowed as the supply or exhaust system is required to function during emergency.

Clause 7.1.11c. : Ventilation system for engine-driven fire pump room and generator room

Section Figure 7.1.11c. - 1
Section
Figure 7.1.11c. - 1

The concern is the stability of the riser ducts, if they pass through one or more floors

Figure 7.1.11c. - 2 : Protected shaft for ducts
Figure 7.1.11c. - 2 : Protected shaft for ducts

As the mechanical ventilation system to generator room and fire pump room is independent of each other, the riser duct for each system shall be separately enclosed in a masonry or drywall shaft and compartmented from the rest of the shaft space containing other ducts or service installations.

Cl.3.8.9a. should also be referred to.

Clause 7.1.11d. : Ventilation system for engine-driven fire pump room and generator room

Figure 7.1.11d.
Figure 7.1.11d.

Ducts serving other areas shall not pass through the fire pump room, generator room and FCC. The above figure shows that the ventilation duct is diverted from traversing the equipment room.

7.1.12

Ventilation system for Fire Command Centre (FCC)

The FCC can either be air-conditioned, naturally ventilated or mechanically ventilated. The air-conditioning or mechanical ventilation shall be independent of each other and any other system serving other parts of the building. Where air-conditioning or mechanical ventilation is provided, the fan coil unit or ventilation fan serving the FCC can be located within the FCC and shall also comply with all of the following requirements:

  1. Supply air shall be drawn directly from the external space and its intake point shall not be less than 5m from any exhaust discharge openings. Exhaust discharge shall also be direct to the external space.

  2. Where the corresponding ducts run outside the FCC, they shall either be enclosed in a structure or be constructed to give at least the same fire rating as the room which they serve or that of the room through which they traverse, whichever is higher. Where the duct risers are required to be enclosed in a protected shaft constructed of masonry or drywall complying with Cl.3.8.7b., they shall be compartmented from the rest of the shaft space containing other ducts or service installations.

  3. No fire damper shall be fitted in either supply or exhaust duct required under this Clause.

  4. A duct serving areas other than the FCC shall not pass through the room.

7.1.13

Exhaust system for kitchen

  1. Provision

    A mechanical exhaust system for the cooking area of a kitchen in a hotel, restaurant, coffee house or the like shall be independent of those serving other parts of the building. It shall also comply with all of the following requirements:

    1. The hood and ducts for the exhaust shall have a clearance of 500mm from unprotected combustible materials.

    2. The exhaust shall discharge directly to the external space and shall not be less than 5m from any air intake openings.

    3. The exhaust duct, where it runs outside the kitchen, shall either be enclosed in a structure or be constructed to give at least the same fire rating as the kitchen or that of the room through which it traverses, whichever is higher. The rating shall apply to fire exposure from both interior and exterior of the duct or structure. Where the duct riser is required to be enclosed in a protected shaft constructed of masonry or drywall complying with Cl.3.8.7b., it shall be compartmented from the rest of the shaft space containing other ducts or services installations.

    4. No fire damper shall be fitted in kitchen exhaust ducts.

Explanations & Illustrations

Clause 7.1.13a.(1) : Exhaust system for kitchen

Section Figure 7.1.13a.(1).
Section
Figure 7.1.13a.(1).

The hood and duct should be separated from other combustible materials by a minimum horizontal clearance of 500mm to prevent ignition through heat radiation. Class F portable fire extinguishers shall be provided according to SS 578.

Clause 7.1.13a.(2) : Exhaust system for kitchen

Section Figure 7.1.13a.(2).: Kitchen exhaust duct
Section
Figure 7.1.13a.(2).: Kitchen exhaust duct

Clause 7.1.13a.(3) : Exhaust system for kitchen

Figure 7.1.13a.(3).- 1
Figure 7.1.13a.(3).- 1

Horizontal run of the exhaust duct outside the kitchen shall be fire-rated with minimum 1-hr fire resistance rating. The 1-hr fire resistance shall be applicable to the inside and outside of the duct.

Figure 7.1.13a.(3) - 2
Figure 7.1.13a.(3) - 2

The protecting structure for protected shaft containing kitchen exhaust duct that pass through one or more floors shall be of masonry construction or drywall.

To eliminate the risk of fire spreading from one compartment to another through burning grease within the duct system, a separate exhaust system is required for each hood located in separate compartments.

Fire dampers are not permitted within the duct system. The effectiveness of fire dampers is questionable as grease on the downstream side would likely ignite before the damper closed. The potential for false operation is also greater than normal and closure other than in a fire situation could have serious consequences. Further it is expected that the majority of kitchen hoods will have their own suppression thereby reducing the risk of fire spreading into the duct.

Continuation of the exhaust system during a fire involving the cooking equipment or in the compartment is not considered to aggravate the situation.

  1. Sharing of kitchen exhaust system

    Sharing of kitchen exhaust system for food and beverage outlets is allowed, provided all of the following conditions are complied with:

    1. For food courts

      1. The food court shall be under a single ownership/ operator.

      2. All kitchen exhaust ducts running outside the food court shall have 1-hr fire resistance rating, or shall not be less than that for the elements of structure, whichever is higher.

    2. For restaurants/small F&B outlets (e.g. snack bars, food kiosks, etc.)

      1. Restaurants and small F&B outlets that are sharing the same kitchen exhaust system shall be located on the same storey and within the aggregate zone area not exceeding 2000m2. The maximum length of the aggregate zone covering from the first to the last restaurant/F&B outlet shall not exceed 50m.

      2. The aggregate floor area of the restaurants and F&B outlets shall not exceed 1000m2.

      3. Common ducts shall be provided with a common exhaust fan.

      4. The building shall be protected by an automatic fire sprinkler system.

      5. The exhaust hood shall be fitted with a wet chemical fire extinguishing system.

      6. The fire rating of the common kitchen exhaust duct running outside the restaurants shall have 1-hr fire resistance rating, or shall not be less than that for the elements of structure, whichever is higher.

        (Note: Kitchen exhaust ducts include both horizontal and vertical ducts.)

Explanations & Illustrations

Clause 7.1.13b.(1) : Exhaust system for kitchen

NRD = Non-rated duct Figure 7.1.13b.(1)
NRD = Non-rated duct
Figure 7.1.13b.(1)

To share a kitchen exhaust system within a food court, it needs to be under a single ownership/operator. In addition, it is also required to make provision for maintenance and cleaning of the exhaust system, i.e. degreased & cleaned regularly.

All kitchen exhaust ducts running outside the food court shall have minimum 1-hr fire resistance rating or not less than that for the elements of structure, whichever is higher.

Clause 7.1.13b.(2) : Exhaust system for kitchen

Figure 7.1.13b.(2)
Figure 7.1.13b.(2)

To be precise, each restaurant shall be provided with its own kitchen exhaust duct. Where the restaurants are located close to each other, on the same floor, within a zone of not more than 2000m2 and have  aggregate floor area of not more than 1000m², the sharing of kitchen exhaust duct is permitted.

Where the restaurants are located far from each other, then the relaxation of common kitchen exhaust duct shall not be applicable. In other words, each restaurant unit shall have its own kitchen exhaust duct.

Note to QP

Clause 7.1.13b.(2)(e)

Wet chemical fire extinguishing systems for exhaust hood(s) shall be of approved type based on international standards such as NFPA 17A. QPs are also reminded to ensure that the premise owners/ operators are aware of the stipulated maintenance regime in the standards.

  1. Kitchen exhaust duct (KED)

    1. A KED running outside a building shall not be located within 3m of any unprotected openings. This separation distance can be reduced to 1.5m if the unprotected opening is on the same plane as the duct. (See Diagram 7.1.13c.(1) - 1 and  2)

    2. Where the distances mentioned above cannot be achieved, a fire resistant construction having at least ½-hr fire resistance shall be placed between the duct and the unprotected opening. (See Diagram 7.1.13c.(2))

    3. A non-fire-rated KED shall not be located above an LPG storage cabinet, unless they are separated from LPG cylinders by a minimum of 2-hr fire-rated masonry construction above and beside the cylinders. (See Diagram 7.1.13c.(3))

    4. The KED shall be located at least 3m from any unprotected LPG cylinders. Non-fire-rated KED shall be located at least 600mm from the vapouriser or any liquid-phase LPG pipeline. (See Diagram 7.1.13c.(4))

    5. Access panels for KED

      KED shall be provided with openings via access panels to facilitate inspection and maintenance, which shall comply with the following:

      1. Access panels shall be provided to allow the interior of the duct to be viewed without the assistance of tools, to facilitate thorough cleaning. The access panels shall not be obstructed by suspended ceilings, cable routes, pipes or other installations.

      2. Access panels shall be located at the sides of the duct.

      3. Access panels are not required at the duct entry, duct discharge, or sections of the duct which are fire-rated or protected with fire-rated enclosure. Excluding these exempted areas, access panels shall be provided at the following locations:

        1. at changes of ducting direction;

        2. if fire extinguishing systems are provided, to facilitate installation and servicing of the fire extinguishing systems;

        3. within 900mm of each side of exhaust fan assemblies;

        4. at least 40mm from all outside edges of the duct or welded seams; and

        5. in addition to compliance with subclause (i) to (iv), access panels shall be located at maximum 3m intervals for horizontal ducting, and at the top and bottom of sections of vertical ducting which runs solely at the building exterior.

      4. Access panels shall be conspicuously marked with the following wording: ACCESS PANEL – DO NOT OBSTRUCT. The lettering shall be at least 25mm in height, in a colour contrasting with the background.

Explanations & Illustrations

Figure 7.1.13c.(5)(a) for KED

Figure 7.1.13c.(5)(a)
Figure 7.1.13c.(5)(a)

If suspended ceiling is provided, an access panel in the ceiling is required to enable access to the KED.

Figure 7.1.13c.(5)(b) for KED

Figure 7.1.13c.(5)(b)
Figure 7.1.13c.(5)(b)

Access panels for KEDs shall be located at the sides, rather than the top surface. 

Figure 7.1.13c.(5)(c) for KED

Figure 7.1.13c.(5)(c)(iii)
Figure 7.1.13c.(5)(c)(iii)

Access panels to be provided at before and after the exhaust fan assembly. 

Figure 7.1.13c.(5)(c)(iv)
Figure 7.1.13c.(5)(c)(iv)

Access panels to be provided at maximum 3m intervals, measured from the edge of the access panels.

Figure 7.1.13c.(5)(c)(v)
Figure 7.1.13c.(5)(c)(v)

Access panels to be provided at top and bottom of sections of vertical ducting which runs solely at building exterior.

  1. Maintenance

    All kitchen exhaust systems shall be properly maintained in accordance with the following: 

    1. The entire (interior and exterior) exhaust duct and kitchen hood shall be degreased and cleaned at least once every 12 months.

    2. The work shall be carried out by a specialist and the records of cleaning and degreasing shall be kept by the owner/ operator for verification. This requirement shall be included in the Fire Safety Instruction Manual. 

Note to QP

Clause 7.1.13d

Building owners, MCSTs and eating outlet operators shall ensure that the entire (interior and exterior) kitchen exhaust duct and kitchen hood shall be degreased and cleaned at least once every 12 months. The work shall be carried out by a specialist and the records of cleaning and degreasing shall be kept by the owner/MCST/operator for verification by the authority having jurisdiction.

7.1.14

Ventilation system for rooms involving use of flammable and explosive substances

  1. Dedicated system

    Mechanical ventilation systems, where required for rooms which involve the use of flammable and explosive substances, shall be independent from those serving other parts of the building. They shall comply with all of the following requirements:

    1. Ventilation system shall consist of exhaust and supply parts with a rate of 20 air changes per hour or any other rates acceptable to the SCDF. The exhaust shall direct to the external space and shall not be less than 5m from any air intake openings.

    2. Where such ducts run outside the room they shall either be enclosed in a structure or be constructed to give at least the same fire rating as the room which they serve or that of the room through which they traverse, whichever is higher. The rating shall apply to fire exposure from both interior and exterior of the duct or structure. Where the duct risers are required to be enclosed in a protected shaft constructed of masonry or drywall complying with Cl.3.8.7b., they shall be compartmented from the rest of the shaft space containing other ducts or service installations.

    3. No fire damper shall be fitted in either a supply or exhaust duct required under this Clause.

    4. Ducts serving other areas shall not pass through rooms involving use of flammable and explosive substances.

  2. Sharing of supply air duct

    A common fire-rated supply air duct can serve various compartments within the same floor level or other floor levels, provided:

    1. the compartments are sprinkler-protected;

    2. the compartments are of the same purpose group;

    3. the duct is fitted with a fire damper where it passes through the wall or floor of each fire compartment; and

    4. a dedicated exhaust duct is provided for individual fire compartments and shall be maintained in operation (with the minimum flow rate) even it is under fire mode situation to prevent smoke entering into other fire compartments.

Explanations & Illustrations

Clause 7.1.14a. : Ventilation system for engine-driven fire pump room and generator room

Section Figure 7.1.14a. - 1
Section
Figure 7.1.14a. - 1

The exhaust system (without fire damper) is required to operate efficiently to remove any gaseous or flammable vapour from the room.

  1. Where the flammable vapour being removed is heavier than air:

    1. At least one air outlet shall be located at a point near a wall, and no higher than 300mm from the floor; and

    2. At least one air inlet shall be located near the opposite wall, no lower than 300mm from the ceiling.

  2. Where the flammable vapour being removed is lighter than air:

    1. At least one air inlet shall be located at a point near a wall, and no higher than 300mm from the floor; and

    2. At least one air outlet shall be located near the opposite wall, no lower than 300mm from the ceiling.

Figure 7.1.14a. - 2
Figure 7.1.14a. - 2

The flammable vapour which is heavier than the air will be discharged via the exhaust system (without damper) as shown above. Do refer to relevant SS for full compliance.

7.1.15

Ventilation system for rooms housing batteries

Rooms housing batteries shall comply with the following requirements:

  1. The batteries shall be of either vented or sealed type.

  2. The room ventilation system shall be designed to limit the maximum concentration of Hydrogen (H2) gas to 1% of the total volume of the room during the worst case event of simultaneous “boost” charging of the batteries. The inlets and outlets of the ventilation system shall be properly located so that there is no stagnant area in the room.

  3. Adequate hydrogen gas detectors shall be provided inside the room to monitor the hydrogen concentration and to activate the fan, if necessary, to ensure that the hydrogen concentration level at any part of the room does not exceed 1% of the total volume of the room. Display panels showing the readings of the detectors shall be located at the entrance to the room. At the same time, an alarm signal shall be sent to a manned station such as security control room, guard house or FCC.

  4. The design of the battery room ventilation shall be in accordance with BS EN IEC 62485-2 & BS EN IEC 62485-3.

  5. For mechanically ventilated battery rooms, the ventilation requirement shall be based on Cl.7.1.15d., or 6 air changes per hour, whichever is higher.

  6. No fire damper shall be provided in the essential ventilation system and ducts passing through other compartments shall have 2-hr fire resistance rating.

  7. Essential fans and associated electrical controls shall be backed up with a secondary source of power supply.

Rationale

Clause 7.1.15b

The revision is in line with NFPA to limit the maximum concentration of hydrogen to 1% of the total volume of the room. The ventilation rate for the room shall be computed in accordance with BS EN IEC 62485 or 6 air changes, whichever is higher.

7.2

Pressurisation for Exit Staircases

7.2.1

Provision

  1. Internal exit staircase

    In any building of which the habitable height exceeds 24m, any internal exit staircases without adequate provision for natural ventilation shall be pressurised to comply with the requirements in this Code. Where the upper part of the staircase is naturally ventilated, its lower part can be provided with mechanical ventilation or pressurisation, whichever is appropriate, in accordance with Cl.2.3.3d.(9).

Explanations & Illustrations

Clause 7.2.1a. : Provision

Section Figure 7.2.1a. - 1
Section
Figure 7.2.1a. - 1

The above clause specifies that all internal staircases without provision for natural ventilation of building having more than 24m in habitable height, shall be provided with pressurisation notwithstanding that smoke-stop lobby is provided. Smoke-stop lobby, if mechanically ventilated, is to be provided with supply air of at least 10 air changes per hour during fire mode. There shall be no exhaust duct extracting air out from the smoke stop lobby.

The need of a dedicated pressurisation system (two fans are recommended, capacity of each fan shall be provided for 50% equipment) for each exit staircase is to prevent failure of one system affecting all exits. Air supply to the exit staircase must be obtained from outside the building to minimise the risk of contamination from smoke resulting from a fire in the building.

Ductwork associated with the discharge of air throughout the staircase may be located within the staircase itself, otherwise it must be protected in a masonry or fire rated shaft.

To achieve the required air flow velocity on any storey, air supplied by the system should be evenly distributed throughout the height of the staircase by ductwork with outlets located not more than two storeys apart. Relief air grilles (pressure relief dampers) could be used for pressure control thereby minimising periods of excessive force to open doors of the staircases. Variable speed fans with pressure relief damper can be accepted as alternative arrangement.

Section Figure 7.2.1a. - 2
Section
Figure 7.2.1a. - 2

Internal exit staircase without adequate ventilation at lower part can be mechanically ventilated provided the lower part shall not exceed 24m in habitable height. Where the lower part exceed 24m, the internal exit staircase shall be pressurised.

Figure 7.2.1a. - 3
Figure 7.2.1a. - 3

Exit staircase (A) is pressurised as it is located within the floor space where natural ventilation cannot be provided. Exit staircase, which is designed without provision for natural ventilation, is pressurised. Smoke-stop lobby is also required to be provided to staircase A.

Figure 7.2.1a. - 4
Figure 7.2.1a. - 4

Exit staircase (B) is pressurised as it is located within the floor space where natural ventilation can not be provided. Exit staircase (C), which is designed without provision for natural ventilation, is pressurised.

Notwithstanding clause 2.2.13(c), smoke-stop lobby is required to be provided to all internal staircases, without provision for natural ventilation, serving building exceeding the habitable height of 24m.

Section Figure 7.2.1a. - 5
Section
Figure 7.2.1a. - 5

Staircase A and transfer staircase A1 are considered as one single staircase sharing a common protected shaft. As staircase A is an internal staircase without openings for natural ventilation, exceeding a habitable height of 24m, it is required to be provided with MV and pressurisation. Since, staircase A1 is acting as a transfer staircase, it shall likewise be MV and pressurised notwithstanding the fact it can be naturally ventilated through external openings. The transfer exit passageway which connects staircases A and A1 should also be MV and pressurised. It is not acceptable to have partial pressurisation to staircase A by introducing a door across the transfer passageway, such that staircase A1 is separated for the provision of natural ventilation. The reason is that by providing a door across the transfer passageway, it would impede the movement of occupants moving towards staircase A1. In this way, the evacuation process within the whole shaft of staircase A would be slowed down.

  1. Basement

    In a building comprising more than four basement storeys, exit staircases connected to a fire lift lobby in basement storeys shall be pressurised to comply with the requirements in this Code.

Explanations & Illustrations

Clause 7.2.1b. : Provision

Section Figure 7.2.1b. - 1
Section
Figure 7.2.1b. - 1

In a building comprising more than 4 basement storeys, the exit staircase adjacent to the fire lift lobby shall be pressurised.

Section Figure 7.2.1b. - 2
Section
Figure 7.2.1b. - 2

Owing to difference in ground levels, staircase B which is serving more than 4 basements shall be located adjacent to a fire lift lobby at each storey.

  1. PG II occupancy

    Where PG II building is provided with a mechanical ventilation system or pressurisation system for its staircase storey shelter, an automatic smoke detection system complying with SS 645 shall be installed. The smoke detector shall be located at the entrance of each exit staircase at every storey, including the non-residential floors. Activation of any smoke detector shall initiate the operation of the mechanical ventilation system or pressurisation system.

Explanations & Illustrations

Clause 7.2.1c. : Provision

Figure 7.2.1c.
Figure 7.2.1c.

Note:

  1. Pure residential buildings are not required to be provided with manual fire alarm or automatic fire alarm system.

  2. Where the stairs are not naturally ventilated and provided with mechanical ventilation or pressurisation system, there shall be a means to activate the mentioned system.

  3. The manual call point provided at every entrance of exit staircase shall initiate the operation of mechanical ventilation or pressurisation system.

7.2.2

Pressurisation level

  1. When in operation, the pressurisation system shall maintain a pressure differential of not less than 50 Pa between the pressurised exit staircase and the occupied area when all doors are closed.

  2. Where a smoke-free lobby is also pressurised, the pressure at the exit staircase shall always be higher.

  3. The force required to open any door against the combined resistance of the pressurising air and the automatic door closing mechanism shall not exceed 110N at the door handle.

Explanation

Clause 7.2.2a. : Pressurisation level

Section Figure 7.2.2a. : Pressure differential between pressurised exit staircase and occupied space
Section
Figure 7.2.2a. : Pressure differential between pressurised exit staircase and occupied space

Clause 7.2.2b. : Pressurisation level

Section Figure 7.2.2b. : Pressure gradient
Section
Figure 7.2.2b. : Pressure gradient

Where the smoke-stop lobby is pressurised, the pressure gradient shall be such that the pressure at the exit staircase is always higher.

Clause 7.2.2c. : Pressurisation level

Figure 7.2.2c.: Maximum force required to open door
Figure 7.2.2c.: Maximum force required to open door

Measurement of the force required to open a stair door can be simply carried out by using a force-measuring in the push or pull mode e.g. a spring balance. The maximum force permitted to open a door in accordance with this Code is 110N. This equates to a force of 11.2kg.

Lever operated latch sets are probably the easiest to measure. Simply hook the spring balance over the lever handle and depress same to unlatch the door, whilst taking care not to exert any push/pull force in doing so. To take a reading, slowly and steadily pull the spring balance and read the scale as the door just starts to open.

7.2.3

Egress velocity

  1. When in operation, the pressurisation system shall maintain an airflow of sufficient velocity through open doors to prevent smoke from entering into the pressurised area.

  2. The flow velocity shall be attained when a combination of two doors from any two successive storeys and the main discharge door are fully open.

  3. The velocity averaged over the full area of each door opening shall not be less than 1.0 m/s.

Explanations & Illustrations

Clause 7.2.3 : Egress velocity

Figure 7.2.3 - 1
Figure 7.2.3 - 1

Air flow velocity of at least 1.0 m/s through open doors is required to prevent smoke from entering into the pressurised staircase.

Figure 7.2.3 - 2
Figure 7.2.3 - 2

The air flow velocity measurement through an open door of a pressurised staircase is taken from the entrance of any of two successive doors held open together with its exiting door at the 1st storey. The resulting value of its airflow velocity through the open door shall not be less than 1m/s.

Tests conducted by the Commonwealth Scientific and Industrial Research Organization (CSIRO) have demonstrated that air flows in excess of 0.8m/s through a door will minimise the spread of smoke against the direction of flow. A minimum air flow rate of 1m/s has therefore been adopted. This air flow must be maintained across the doorway providing egress from the fire-affected storey into the staircase during a fire. Initially, building occupants from both the fire floor and the floor above the fire floor will evacuate the building and, depending on the fire situation, this may be simultaneous operation.

The requirement for two floor doors and the 1st storey door (opening into the exterior) to be open the same time has two applications:

  1. When the fire fighters arrive and use the staircase for fire fighting operations, hose connection to the landing valves located on a floor would be carried out. Initially hose will be run from the floor below up the staircase and onto the fire floor hence a minimum opening of two doors is involved.

  2. All required exit staircases must be usable at the same time as either fire fighters or evacuating occupants will be using any of them to exit at the 1st storey door to the street or external safe open area. Thus the final exit door would remain in the open position at all times.

7.2.4

Leakages

  1. The rate of supply of pressurised air to the pressurised areas shall be sufficient to make up for loss through leakages into the unpressurised surroundings.

  2. Adequate relief of leaked air out of the occupied area shall be provided to avoid a pressure build-up in this area. The relief can be in the form of perimeter leakages or purpose built extraction systems.

Explanation

Clause 7.2.4 : Leakages

Figure 7.2.4
Figure 7.2.4

Pressurised air could leak through areas such as gaps around doors, windows, other ventilation openings and other places where air will escape.

In the above figure, pressurised air from the exit staircase leaks into the smoke-stop lobby (A1) and occupancy areas (A2 & A3).

To avoid a pressure built-up in the occupancy area, adequate measures shall be taken to allow air leakage, e.g. through windows A4 to A7. A pressure build-up would create difficulty in opening the doors to the occupancy area.

The following are possible ways in which the escape of pressurising air can be achieved:

  1. by window leakage, or

  2. by specially provided vents at the building periphery, or

  3. by the provision of vertical shaft, or

  4. by mechanically operated extraction.

7.2.5

Distribution of pressurising air

  1. The number and distribution of injection points for supply of pressurising air to the exit staircase should ensure an even pressure profile complying with Cl.7.2.2.

  2. The arrangement of the injection points and the control of the pressurisation system shall be such that when the opening of doors or other factors cause significant variations in pressure difference, the condition in Cl.7.2.2 shall be restored as soon as practicable.

Explanations & Illustrations

Clause 7.2.5 : Distribution of pressurising air

Section Figure 7.2.5
Section
Figure 7.2.5

The above installation is not acceptable as over pressurisation would occur at the upper portion of the staircase. Supply air to the staircase should be well distributed by a vertical supply duct, preferably serving all the levels of the staircase.

An example of an arrangement showing good distribution of supply air can be seen in Figure 7.2.6.

7.2.6

Pressurisation equipment and controls

  1. All the equipment and the relevant controls associated with the pressurisation system shall be designed and installed to ensure satisfactory operation in the event of a fire.

  2. Supply air for the pressurisation system shall be drawn directly from the external space and its intake shall not be less than 5m from any exhaust discharge openings.

  3. The pressurisation system shall be automatically activated by the building fire alarm system. In addition, a remote manual start-stop switch shall be made available to firefighters at the FCC, or at the fire alarm panel where there is no FCC. Visual indication of the operation status of the pressurisation system shall be provided.

Explanations & Illustrations

Clause 7.2.6 : Pressurisation equipment & controls

Section Figure 7.2.6
Section
Figure 7.2.6

The “start-stop” switch is required to be provided in the FCC, or at the main fire alarm panel where there is no FCC. The rationale is to provide the firefighters greater ease and better control in operating the supply air fan to the staircase.

This arrangement facilitate the supply air fan to be shut from the designated remote “start-stop" location. The supply air fan can then be restarted anytime when required.

7.3

Pressurisation of Internal Corridors In Hotels

7.3.1
  1. Where internal corridors in hotels are required to be pressurised in compliance with Cl.9.7.2a.(3), the pressure within such corridors shall be higher than that in the guest rooms by 12.5 Pa. Corridor pressurisation shall be activated for the floor on fire and two floors above.

  2. The pressure within the smoke-free lobby/ fire lift lobby serving these internal corridors shall be higher than that of the internal corridors by 12.5 Pa. The pressurisation fans serving the smoke-free lobby/ fire lift lobby shall activate on all floors during a fire.

  3. Pressure within the internal exit staircases shall comply with Cl.7.2.2a..

Explanations & Illustrations

Clause 7.3.1 : Pressure differences

Figure 7.3.1 - 1
Figure 7.3.1 - 1

Provision of pressurisation to the internal corridor would help to check the migration of smoke from any of the guest rooms. The pressure gradient shall be such that :P1>P2>P3

Acceptable More than 4 storeys Figure 7.3.1 - 2 : Internal staircase with MV smoke-stop lobby
Acceptable
More than 4 storeys
Figure 7.3.1 - 2 : Internal staircase with MV smoke-stop lobby

The above figure illustrates a mechanical ventilated smoke stop lobby and an internal staircase to be pressurised accordingly. The pressure gradient shall be such that the pressure at the exit staircase shall always be higher.

Acceptable More than 4 storeys Figure 7.3.1 - 3 : External staircase with MV smoke-stop lobby
Acceptable
More than 4 storeys
Figure 7.3.1 - 3 : External staircase with MV smoke-stop lobby

The smoke-stop lobby shall be provided with mechanical ventilation and the staircase shall be treated as an external staircase. The external staircase shall be provided with uninterrupted permanent openings having minimum 50% of the staircase plan area (louvre is not allowed).

Acceptable More than 4 storeys Figure 7.3.1 - 4 : External staircase with NV smoke-stop lobby
Acceptable
More than 4 storeys
Figure 7.3.1 - 4 : External staircase with NV smoke-stop lobby

The above figure illustrates a naturally ventilated smoke-stop lobby and external staircase. The smoke-stop lobby shall be provided with minimum 15% external openings. The external staircase shall be provided with uninterrupted permanent openings having minimum 50% of the staircase plan area (louvre is not allowed).

Not more than 4 storeys Acceptable Figure 7.3.1 - 5 : External staircase without smoke-stop lobby
Not more than 4 storeys
Acceptable
Figure 7.3.1 - 5 : External staircase without smoke-stop lobby

The internal corridor leading to the exit should be via a minimum 1-hr fire resistance door. The external staircase shall be provided with uninterrupted permanent openings having 50% of the staircase plan area (louvre is not allowed).

Not more than 4 storeys Acceptable Figure 7.3.1 - 6 : Internal staircase without smoke-stop lobby
Not more than 4 storeys
Acceptable
Figure 7.3.1 - 6 : Internal staircase without smoke-stop lobby

In the above figure, the provision of smoke-stop lobby is not required by virtue of its height under Cl.2.2.13. The staircase is an internal staircase, as such it shall be pressurised to have a higher pressure differential than the internal corridor.

Not more than 4 storeys Figure 7.3.1 - 7 : Pressurisation system for hotel
Not more than 4 storeys
Figure 7.3.1 - 7 : Pressurisation system for hotel

The above figure shows a simple pressurisation system suitable for small hotels. It consists of fans, which are connected to smoke sensitive device so that they operate in fire emergency. The corridor shall be provided with pressurisation to maintain a positive pressure. The power and capacity of the fan is calculated after evaluation of air leakage factors, so that an adequate pressure differential can be developed between the corridor and the guest rooms.

For effective pressurisation, there must be sufficient leakage through the external envelope of the building so that the pressure in the fire room will not reach the same pressure level with the pressure in the protected corridor.

7.4

Smoke Control System

7.4.1

Provision

  1. An engineered smoke control system as specified in Cl.7.4.5 shall be provided where:

    1. the requirements for compartmentation specified in Cl.3.2.1Cl.3.2.4a. and Cl.3.2.4b. are relaxed under the conditions in Cl.3.2.6 for Atrium spaces in a building, or

    2. the total floor area of any compartment in a building or part of a building exceeds 5000m², or

Explanations & Illustrations

Clause 7.4.1a.(1)&(2) : Provision

Section Figure 7.4.1a.(1) & (2) : Atrium smoke control system
Section
Figure 7.4.1a.(1) & (2) : Atrium smoke control system

Before the use of engineered smoke control system is allowed in any proposal, the SCDF shall be satisfied that the compartment height of atrium is connecting more than 3 storeys below the habitable height of 24m;

Where more than 3 storeys are interconnected and the size and volume is relaxed with provision of atrium smoke control system, only the first basement is allowed to form part of the upper storey.

A smoke control system shall be provided to any compartment in a building or part of a building which has a total floor area greater than 5000m². Smoke from any fire in such compartment would easily find its way into escape routes leading to exits or exit staircases. The activation of the smoke control system would ensure that the smoke layer would not be lower than 1.8m from floor level to allow occupants to find their ways to the exits or exit staircases.

Note to QP

Clause 7.4.1a.(1)

The QPs are required to consult SCDF to seek consent before making any plan submission. The consent that is given by SCDF to allow the use of engineered smoke control system in the proposal shall only relate to the relaxation on the compliance with the above requirements under Cl.3.2.1 and Cl.3.2.4a. and b. of the Fire Code.

  1. -

    1. the total aggregate floor area of all basement storeys exceeds 2000m², except in any of the following situations:

      1. Where the basement or a portion of the basement is used as a car park, the car park shall comply with the requirements of smoke purging system in accordance with Cl.7.4.3, provided it is compartmented from the rest of the basement.

      2. Where a plant/ equipment room with floor area not exceeding 250m² is compartmented from rest of the basement, two doors remotely located from each other for better reach in firefighting operations shall be provided. The provision of a single door opening for this room is permitted provided the most remote part of the room is less than 8m from the door, and the equipment found inside this room, does not obstruct the throw of a water jet from a firefighting hose.

      3. Where a plant/ equipment room with floor area not exceeding 2000m², is provided with smoke vent in accordance with Cl.7.4.2 or smoke purging system in accordance with Cl.7.4.3.

      4. Where a compartmented service area comprising storerooms or workshops (restricted to staff only) is provided with smoke vent in accordance with Cl.7.4.2, or smoke purging system in accordance with Cl.7.4.3.

      5. Where the basement of a residential development is used as a car park, one office intended for ancillary use is permitted in the car park. The office shall be provided with smoke purging system in accordance with Cl.7.4.3 and compartmented from the rest of the basement. The office floor area shall not exceed 40m².

Explanations & Illustrations

Clause 7.4.1a.(3)(a) : Provision

Section Figure 7.4.1a.(3)(a)
Section
Figure 7.4.1a.(3)(a)

If the total floor area of basements 1 & 2 (other usage + car park) >2000m², engineered smoke control is required to be provided in the basement storeys; except the car parking areas in basement 1 & 2 which need to be provided with smoke purging system under Cl.7.4.3.

Clause 7.4.1a.(3)(b) : Provision

Figure 7.4.1a.(3)(b)
Figure 7.4.1a.(3)(b)

Where the plant/equipment room is not greater than 250m², firefighters can fight a fire in that room from its doorway.

Clause 7.4.1a.(3)(c) : Provision

Figure 7.4.1a.(3)(c)
Figure 7.4.1a.(3)(c)

Where floor area of the plant/equipment room is in excess of 250m², but not exceeding 2000m², provision of smoke vents in accordance to Cl.7.4.2 or smoke purging system in accordance with Cl.7.4.3 would be acceptable.

Cl.7.4.1a.(3)(c) is meant to grant relaxation over the general requirement as service rooms are usually of low occupancy load. Common areas outside the plant rooms/service rooms shall be provided with engineered smoke control system.

Clause 7.4.1a.(3)(d) : Provision

Figure 7.4.1a.(3)(d) - 1
Figure 7.4.1a.(3)(d) - 1

The above clause is mainly applicable to hotel building. Service areas such as laundries, stores and workshops that are restricted to staff only shall be compartmented. The total area of these compartments shall not exceed 2000m² (per storey basis). Each compartment shall be provided with smoke venting or smoke purging system.

Figure 7.4.1a.(3)(d) - 2
Figure 7.4.1a.(3)(d) - 2
  1. Service areas in basement storey used as laundry area are areas that are normally occupied.

  2. Hence, smoke dilution of at least 9 air charges may not suffice.

  3. Adequate level of visibility and smoke dispersal shall be maintained for these areas to facilitate escape.

  4. Engineered smoke control system shall be provided.

  1. A smoke vent in accordance with Cl.7.4.2 shall be provided if the total aggregate floor area of all basement storeys does not exceed 2000m², except for PG I buildings . In lieu of smoke vents, a smoke purging system or an engineered smoke control system is permissible for car parks or other occupancies respectively.

Explanations & Illustrations

Clause 7.4.1b. : Provision

Figure 7.4.1b. - 1
Figure 7.4.1b. - 1
Figure 7.4.1b. - 2
Figure 7.4.1b. - 2

Total aggregate floor area of basement storeys = Area of car park + staircases + services area (telecommunication room, transformer room etc.) + plant/equipment room of basement 1 + area of whole basement 2.

If total aggregate area< 2000m² (see Cl.7.4.2). If total aggregate area>2000m² (engineered smoke control system or smoke purging is required), See also Cl.7.4.3 and  Cl.7.4.1a.(3)(b) & (c)

7.4.2

Smoke vent

Smoke vents shall be adequately distributed along the perimeter of the space served, and its outlets shall be easily accessible during firefighting and rescue operations. Smoke vents shall comply with the following requirements:

  1. the number and their sizes shall be such that the aggregate effective vent openings shall not be less than 2.5% of the floor area served;

  2. the vent outlets, if covered under normal conditions, shall be openable in case of fire;

  3. the position of all vent outlets and the areas they serve shall be suitably indicated adjacent to such outlets;

  4. where ducts are required to connect the vent to outlets, the ducts shall either be enclosed in structure or be constructed to give at least 1-hr fire resistance rating; and

  5. separate ducts and vent outlets shall be provided for each storey.

Explanations & Illustrations

Clause 7.4.2 : Smoke vent

Figure 7.4.2 : Smoke vents for basement occupancies
Figure 7.4.2 : Smoke vents for basement occupancies
  1. Smoke ventilation shafts where extending through storeys above, shall be enclosed with imperforate walls having minimum 1-hr fire resistance.

  2. Separate smoke ventilation shafts and outlets shall be provided for each basement storey.

  3. Smoke venting outlets shall be so arranged that a through draught can be created.

  4. Outlets covered by stalled boards, or approved type pavement lights shall be readily openable/breakable.

  5. The positions of all smoke vent outlets and the basement level or areas they serve shall be suitably indicated on the external face of the building adjacent to such outlets.

7.4.3

Smoke purging system

Smoke purging system, where permitted under this Code in buildings, shall conform to all of the following requirements:

  1. The smoke purging system shall be independent of any other system serving other parts of the building.

  2. The purging system’s purge rate shall be at least 9 air changes per hour.

  3. The purging system shall be activated automatically by the building fire alarm system. In addition, a remote manual start-stop switch shall be located at the FCC, or at main fire alarm panel on first storey (where there is no FCC in the building). Visual indication of the operation status of the smoke purging system shall also be provided with this remote control.

  4. Supply air shall be drawn directly from the external space and its intake shall not be less than 5m from any exhaust discharge openings. Outlets for the supply air shall be adequately distributed over the area served.

  5. Where there is natural ventilation for the area served based upon evenly distributed openings equal to not less than 2.5% of the floor area of a given storey, such natural ventilation can be considered a satisfactory substitute for the supply part of the smoke purging system.

  6. Replacement air shall be provided and if it is supplied by a separate mechanical system, such a system shall be connected to a secondary power supply.

  7. Exhaust ducts shall be fabricated from heavy gauge steel of at least 1.2mm thickness.

  8. The exhaust fan shall be capable of operating effectively at 250ºC for 2 hours and be connected to a secondary power supply.

Explanations & Illustrations

Clause 7.4.3a.-d. : Smoke purging system

Section Figure 7.4.3a.-d. : Smoke purging system with ducted supply air intake
Section
Figure 7.4.3a.-d. : Smoke purging system with ducted supply air intake

The reasons for locating the remote manual start/stop switch in the FCC or main fire alarm panel on 1st storey (where FCC is not available) are:

  1. to allow firefighting personnel to shut down the supply air system temporarily in the event that smoke is being drawn into the lobby through the outdoor air intake; and

  2. to allow firefighting personnel to activate the supply sir system should the fire alarm system fail to automatically activate the supply air system.

Clause 7.4.3e.-h. : Smoke purging system

Section Figure 7.4.3e.-h. : Smoke purging system with natural opening for supply air intake
Section
Figure 7.4.3e.-h. : Smoke purging system with natural opening for supply air intake

Exhaust fans shall be rated at minimum 250°C. Supply air part of the smoke purging system is provided via opening to the external air. The openings provided for supply air shall not be less than 2.5% of the floor area of each basement storey. Ramp openings, voids over car parking areas are considered acceptable openings for fresh air supply.

Where a smoke purging system consists of a supply and exhaust , both of which shall be designed such that each can operate in two sections.

The capacity of each section shall be sufficient to provide half the air changes required. Each section of the smoke purging system shall so constructed that in the event of failure of one section (exhaust part or supply part), the other section shall continue to operate. This can prevent failure of the system caused by failure of one single fan.

The exhaust and supply parts shall be electrically interlocked so that failure of any section of the exhaust part shall automatically shut down the corresponding section of the supply part, which can prevent total failure of the smoke purging system caused by the failure of one single fan.

In the event that any exhaust fan fails to run or is shut down for maintenance, the corresponding supply fan should not run so as to prevent fresh air from being pumped into the basement. The interlocking arrangement will not apply if smoke purging system consists of only the exhaust part. However, the exhaust system shall also be designed into two section as per the above.

7.4.4

Ductless jet fan system

  1. General

    This system can be used in lieu of a smoke purging system for conventional car parks where passenger cars/light weight vehicles are parked alongside each other with common driveways. It is not intended for mechanised car park systems or other forms of car parking systems.

  2. Provision of sprinkler system

    1. The basement car park shall be sprinkler-protected in accordance with the SS CP 52.

    2. The arrangement of the sprinkler heads and the jet fans shall be such that, upon the operation of the jet fans, the effect on the spray pattern of the sprinklers is minimised.

  3. Zoning of car park

    1. All car park spaces shall be divided into smoke control zones with each zone not larger than 2000m(excluding plant rooms and circulation spaces) for the purpose of smoke containment and quicker location of fire. A commissioning test will be carried out using hot smoke to demonstrate that smoke can be contained within each zone and channelled to the extract fans.

    2. Each smoke control zone shall have its own jet fan system (fresh air fans, exhaust air fans and jet fans) to purge smoke from the affected zone. The ducts shall be fabricated from heavy steel gauge steel of 1.2mm thickness. Alternatively, sharing of the fresh air and exhaust air fans is permitted provided the fans, wiring and control panel are protected with at least 1-hr fire resistance rating. The exhaust fan system shall also be designed to run in at least two parts, such that the total exhaust capacity does not fall below 100% of the required rate of extract for the zones affected in the event of failure of any one part. This requirement is also applicable for mechanised supply fan system, if it is used.

  4. Jet fan system

    1. The jet fan system shall be activated by the sprinkler system serving the basement car park level and any other areas located within the same level. The activation of the jet fan system shall be confined to the smoke control zone on fire and all its adjacent zones. A firefighter cut-off and activation (override) switch shall be provided at the FCC. As an alternative form of fan activation, the use of smoke detectors to activate the jet fan system is allowed, provided:

      1. the detectors are positioned at the effective mid-range of the jet fan profile;

      2. in-duct smoke detector is located at the start point of the exhaust duct; and

      3. jet fan system shall only operate upon activation of two smoke detectors. This is to minimise false alarms.

    2. The jet fan system shall be provided with a secondary source of power supply through automatic operation of an emergency generator in case of failure of the primary power supply source.

    3. The jet fans shall be distributed at a spacing of 2⁄3 of the tested effective range of each jet fan. The tested effective range of the jet fan shall be taken as the distance up to the point at 0.2m/s of the air-velocity distribution profile.

    4. The minimum headroom for the installation of the jet fan system is 3m.

    5. The interaction of the various components of the jet fan system shall be as follows:

      1. Each group of exhaust fans for each smoke control zone shall be interlocked with its corresponding groups of jet fans for that zone.

      2. If the group of exhaust fans stops/ fails in any smoke control zone, the corresponding group of jet fans in that zone shall stop. But if any of the exhaust fans is still in operation in a particular smoke control zone, all the jet fans in that zone shall continue to operate.

      3. The exhaust fan shall continue to run even if any corresponding group of jet fans fails.

      4. The other groups of jet fans shall continue to run even if any one group of jet fans fails.

      5. If the fire alarm signal is isolated, the exhaust fans and jet fans shall continue to run at high speed. If the fans are manually restarted, both the exhaust fans and jet fans shall continue to run at high speed until they are set to low speed at the field control panel.

    6. The jet fan system shall be independent of any systems serving other parts of the building.

    7. The jet fan system design shall be such that the bulk air velocity induced by the jet fans is sufficient to stop the advance of the ceiling jet within 5m from the fire location in the direction opposite to the induced bulk air flow.

    8. The smoke control sub-panel in each smoke control zone is to be connected to the main smoke control panel, such that any isolation of jet fan system at a particular zone is automatically displayed at the main smoke control panel.

    9. The car park main smoke control panel at the FCC/ Guard house and remote local panel for the supply and exhaust fans shall indicate, by means of indicator lights, whether the fans are on low or high speed. The panels are also required to have the individual group of jet fans indication lights interlocked with the main exhaust fans in the respective smoke control zones.

    10. In the event of failure of the primary source of power supply and subsequent operation of the secondary power supply, the mode of operation of the jet fan system during the fire mode shall follow that prior to the failure of the primary power supply. For example, if the operation of jet fan system in a particular smoke control zone is switched off by the firefighter during fire mode condition and the primary source of power fails, the subsequent operation of the secondary power supply shall be such that the jet fan system remains in the previous fire mode condition, i.e., non-operational mode for that smoke control zone, while the other smoke control zones resume operation.

    11. The jet fan system design shall take into consideration the presence of any down-stand beams and other obstructions that are of depths of more than 1/10 of the car park floor to ceiling height so as to account for any resistance to airflow.

    12. On activation of the jet fan system, the movement of smoke towards the extraction point(s) shall not adversely affect the means of escape and cause smoke to be blown into the lobby area or exit staircases.

    13. The operation of the jet fan system should be such that there are no stagnant areas where smoke can accumulate in the event of fire.

    14. The operation of the jet fan system shall not cause the volume of air movement to be greater than that volume extracted by the main exhaust fans.

    15. There shall be at least one viable approach route (i.e. where acceptance criteria for firefighters are in accordance with Cl.7.4.4g. and Diagram 7.4.4e.(4)-2) for the firefighters to any possible fire location up to a distance of 5m from that fire. As such, information as to the viable approach route shall be displayed at the main fire alarm panel. This can be achieved by arranging the sprinkler control zone to correspond with that of the smoke control zone. Upon detection of the fire within a particular smoke control zone/ sprinkler zone, reference can be made to the display showing the viable approach route for that particular smoke control zone.

  5. Wiring arrangement of jet fans

    1. All jet fans shall be connected to the local jet fan control panel in groups of not more than three jet fans.

    2. Each group will be connected by fire-rated cabling.

    3. Each group of jet fans will be protected by a separate MCB (main circuit breaker), with power supply compliant with SS 638, to prevent the failure of all the jet fans at once due to tripping of the main RCB, e.g., due to overloading.

    4. The jet fans shall also be wired in a zigzag configuration and no two consecutive jet fans in a straight line are to be wired in the same group. In the event of failure of one group of jet fans, the next corresponding group will be able to drive the smoke towards the exhaust location to be extracted (see Diagram 7.4.4e.(4) - 1 & 2). Should one group of jet fans fail, all other groups shall still continue to run.

    5. The location of the local control panel for the operation of the jet fans within each zone shall be in a relatively safe area within the zone and be spaced as least 5m apart from the local control panels of adjacent zones. This is to minimise the risk of a fire affecting all the control panels if they be spaced closely together, and thus rendering the ineffectiveness of the jet fan system.

  6. Provision of supply air

    1. Supply air to the car park can be provided via mechanised supply air fans or by permanent openings of at least 2.5% of the floor area. Whichever is used, the maximum inlet air speed shall be 2m/s to prevent recirculation of smoke.

    2. The air velocity within escape routes and ramps shall not exceed 5m/s to prevent escapees from being hindered by the air flow.

    3. The replacement air intakes shall face away from any smoke exhaust points and be sited at least 5m apart so as to prevent recirculation of smoke. If the supply and exhaust louvers are located on the same façade of the building, they shall also be sited at least 5m apart.

    4. The replacement air intake shall be located on the opposing end of the smoke exhaust points so that there is no opposing flow between the supply air and the smoke that is drawn towards the exhaust fan.

  7. Exhaust fan design

    1. The car park shall be provided with at least 12 air changes per hour during a fire. A lower air change not less than 9 air changes can be permitted provided the acceptance criteria stipulated in the Cl.7.4.4g.(1)(b) can be achieved through fire modelling:

      1. Hot smoke test/ CFD fire modelling
        The effectiveness of the jet fans system design shall be demonstrated using hot smoke test in accordance with Cl.7.4.4j.. The heat release rate of the fuel load for the hot smoke test shall be at least 1MW. The relevant PE or Fire Safety Engineer should decide on the fire location(s) that is (are) deemed most onerous with justification. In addition to the hot smoke test, Computational Fluid Dynamics (CFD) fire modelling will also be required in the following instances:

        1. If air change per hour is smaller than 12.

        2. If there are general goods vehicle or coaches where design fire size exceeds 4 MW (i.e., car fire).

        3. If replacement air is a combination of natural and mechanical means.

        4. If spacing of jet fans is more than 2/3 of the tested effective range.

          The CFD study is to be endorsed by a Fire Safety Engineer (FSE) to verify the conformance of the jet fans system with the acceptance criteria as stipulated in Cl.7.4.4g.(1)(b). The FSE is also required to put up a fire engineering report. Some of the accepted fire modelling software includes FDS, Swift-AVL, Fluent and Pheonics.

      2. Acceptance criteria

        1. Not more than 1000m2 of the car park space can be smoke-logged for at least 20 mins, regardless of whether the fire is located within the smoke control zone or across the zone boundaries (Note: After the 20 mins duration, smoke is expected to remain confined within the 1000m2 area). Within this smoke-logged area, there shall be at least 1 viable route for the firefighters where the following conditions are satisfied:
          *Smoke temperature shall not exceed 250oC at a height of 1.7m from floor level.
          *Visibility shall not be less than 5m at a height of 1.7m from floor level.
          These conditions shall commence at a distance of 5m from the fire location in the direction opposite to the induced bulk air flow induced by the jet fans. All other areas outside the smoke-logged area shall be kept substantially free from smoke i.e. smoke temperature not more than 60oC and visibility of at least 25m (Diagrams 7.4.4e (4) - 1 & 2).
          (Note: If hot smoke test is performed, assessment is to be made on the operation of the jet fans system, movement of smoke towards the extraction points and smoke spread. The latter 2 aspects can be generally verified using the above visibility criterion. The temperature criterion need not be verified in view of the nature of the hot smoke test.)

      3. CFD fire modelling input parameters

        1. Fire Size
          The design fire size shall be based on at least 4MW steady-state fire (i.e., car fire). For general goods vehicle, the design fire size shall be based on at least 10MW steady state fire (FSE is expected to provide justification for the bigger fire size other than the car fire).

        2. Type of fire

          The type of fire shall be flaming polyurethane.

        3. Location of fire

          Generally, the fire should be located furthest away from the exhaust points and in between zones. The relevant PE or Fire Safety Engineer should decide on the fire location(s) that is (are) deemed most onerous with justification.

        4. Down-stand beams and other obstruction
          The CFD model shall take into consideration the presence of any down-stand beams and other obstruction that are of depths of more than 1/10 of the car park floor to ceiling height so as to account for any resistance to airflow and turbulence.

        5. Jet fan velocity profile
          Validation model of the velocity profile is to be carried out for a single jet fan. The data from the model shall be compared against physical test data. 
          As such, the jet fan shall be tested for velocity profile by an accredited testing laboratory for comparison with the simulated velocity profile. The test report is to be attached to the Fire Engineering Report. The equation to be used for the deviation between the CFD profile and actual test profile is as follows:
          Equation : Deviation = [(A-B) / B] X 100%
          Where :
          A = distance/width/height from CFD profile
          B = distance/width/height from actual test profile
          The deviation of the distance, width and height of the actual profile from the simulated profile at the various air velocities should be within 10%.

        6. Duration of fire simulation

          The duration of the fire simulation shall be at least 20 mins.

        7. Sprinkler activation
          The model shall assume there is no sprinkler activation for the design fire size specified in Cl.7.4.4g.(1)(c)(i).

        8. Grid resolution
          The grid size to be used in the fire model shall not be larger than 200mm X 200mm X 200mm in the smoke control zone where fire is located and its adjacent zones. Other than these zones, the grid size shall not be larger than 400mm X 400mm X 400mm. Alternatively, the relevant PE or FSE undertakes a grid resolution study to ascertain the appropriate grid size needed for the fire size and smoke flows modelled (e.g., outcome of study showing that additional resolution does not make much of a difference to the results).

        9. Sensitivity study

          A sensitivity study is to be carried out to show the impact of 1 group of jet fan failure nearest the fire on the overall effectiveness of the jet fans system. This study is applicable to both fire modelling and hot smoke test. Notwithstanding the failure of 1 group of jet fans, the acceptance criteria must still be maintained.

    2. The capacity of the exhaust fan and any associated ducting shall be calculated on the basis that the pressure in the car park close to the extract points is equal to the external atmospheric pressure.

    3. Each smoke control zone of the car park shall have its own exhaust fan system. The exhaust fan system in each zone shall be designed to run in at least two parts, such that the total exhaust capacity does not fall below 50% of the required rate of extract in the event of failure of any one part, and that a fault or failure of the exhaust fan system in one zone will not affect the operation of the exhaust fan system in the other zones. The above requirement is also applicable for mechanised supply fan systems, where used.

      (Note: If there is sharing of the exhaust air fans, see Cl.7.4.4c.(2))

    4. The smoke discharge points shall be located such that the smoke extracted from the smoke exhaust fans does not affect any occupied area or means of escape at the level where smoke is discharged.

  8. Fire resistance of jet fan system

    The jet fan system, such as the mechanised air supply fans, smoke exhaust fans, jet fans, duct works and wiring shall be capable of operating effectively at 250°C for 2 hours. The fans, ducts and wiring shall be tested in accordance with EN 12101-3, BS 476: Part 24 and SS 299, respectively.

  9. Operations and maintenance manual

    An operations and maintenance manual shall be attached. The manual shall contain the roles and responsibilities of the building owner/ operator, the restrictions placed on the building, identification of the sub-systems, servicing and maintenance plan, fault identification, etc. The manual can also be used as a guide for future renovations and changes to the building.

  10. Commissioning test

    The Registered Inspector who carries out commissioning test of the jet fans system may make reference to Table 2 of BS 7346 - Part 7 as a guide. When hot smoke test is performed, the PE/ FSE shall use a test fire size of 1MW. Reference may be made to AS 4391 on hot smoke test and PE is advised to make reference on how the test can be prepared and carried out in a proper manner.

7.4.5

Engineered smoke control system

  1. Acceptable design guidance

    The engineered smoke control system shall be in the form of a smoke ventilation system by natural or mechanical extraction designed in accordance with BR 186, BR 258, BR 368 and other acceptable standards:

  2. Sprinkler system

    A building provided with an engineered smoke control system shall be sprinkler-protected.

Explanations & Illustrations

Clause 7.4.5a. : Engineered smoke control system

BR 186 and BR 258 and subsequent revisions / amendments have been adopted as acceptable design guides for engineering smoke control systems. Other acceptable standards such as NFPA 92A may be adopted, taking into consideration that the basic requirements of smoke control system in the Fire Code should be strictly complied with. In the case of differences in requirement between BR 186 / 258 and NFPA 92A, e.g. classification of fire size, the clear height of smoke layer base, the QPs should consult the SCDF to determine which requirement to adopt before building plan submission. Other acceptable standards referred to from time to time will be evaluated and QPs will be informed through SCDF’s circulars.

Rationale

Clause 7.4.5b

The main reason that sprinkler system must be provided is to control the fire size. The sprinkler head spacing in respect of both hazard and classification determines the size of a fire, in area and perimeter. The activation of sprinkler heads would, besides controlling the fire size, help to reduce the build-up of heat and toxic gases, which can lead to flashover and smoke explosions. Based on research, if the fire is not sprinkler controlled, the fire size would be unlimited and therefore, fire size could not be established.

  1. Fire size

    1. Non-industrial buildings

      The capacity of the engineered smoke control system shall be calculated based on the incidence of a likely maximum fire size for a sprinkler controlled fire as recommended in the following table:

      TABLE 7.4.5c.(1) : FIRE SIZE FOR NON- INDUSTRIAL BUILDINGS

      Occupancy (Sprinkler-protected)

      Fire Size

      Heat Output (MW)

      Perimeter of Fire (m)

      Shops

      5

      12

      Shops (fast response sprinklers)

      2.5

      9

      Offices

      1

      14

      Hotel Guest Room

      0.5

      6

      Hotel Public Areas

      2.5

      12

      Assembly Occupancy with Fixed Seating

      2.5

      12

    2. Industrial buildings

      The requirements for design fire size are applicable to sprinkler- protected industrial premises (factory and warehouse) without in-rack sprinklers and limited to the design of smoke control system based on Cl.7.4.

      1. Fire growth

        The fire growth can be evaluated by the following generic fire growth curve (also referred to as ‘t2 fire’), that represents the general types of combustible material present within an enclosure:

         

        Qmax = ∝ (t-ti)2 ------------------------------------- equation (1)
        where:
        Qmax = heat release rate (kW);
        ∝ = fire growth parameter (kJ/s3);
        t = time (s);
        ti = time of ignition (s) (taken here as zero)

        The fire growth parameter varies with the fire load density and the fire load configuration factor. However, for purpose of design, fire growth parameter can be generally defined as follows:

        TABLE 7.4.5c.(2)(A) : FIRE GROWTH PARAMETER FOR INDUSTRIAL BUILDINGS

        Fire growth rate

        Fire growth parameter (kJ/s3)

        Time for Qg = 1MW (s)

        Slow

        0.0029

        600

        Medium

        0.012

        300

        Fast

        0.047

        150

        Ultra fast

        0.188

        75

        Note:

        The fire growth rate that is applicable through available literature or standard such as the SFPE Handbook shall be adopted. In the instance where the fire growth rate lies in between the range as stated above, the more conservative fire growth rate is to be used.

      2. Design fire – sprinkler-protected

        1. The heat output of the design fire is assumed to increase according to equation (1) until sprinkler operation is deemed to occur at time t8. Following sprinkler operation, the heat output of the fire is considered to remain constant.

        2. The capacity of the smoke control system shall be based on the fire size that is controlled by activation of 2nd ring of sprinklers.

        3. The operation of the sprinkler system at ts and the corresponding fire size can be determined by hand calculations based on fire engineering principles or the use of fire engineering tools such as FPETool from National Institute of Standards and Technology (NIST). Whichever approach is used, the following design factors governing its calculation are as follows:

          • Rate of fire growth
            The type of fuel load and its configuration in the premises shall govern the rate of fire growth which can be represented using equation (1) and Table 7.4.5c.(2)(a).

          • Sprinkler response time index (RTI)
            The RTI is the thermal sensitivity of the sprinkler and shall be based on the manufacturer’s specification.
            Example:
            Standard response sprinkler – 105m0.5s0.5;
            Fast response sprinkler - 50m 0.5s0.5;
            ESFR - 26m0.5s0.5

          • Temperature rating of sprinkler
            The operating temperature of the sprinklers shall be based on SS CP 52 (e.g., 141°C or 68°C).

          • Ambient temperature
            Room temperature for air-conditioned spaces and non-air conditioned spaces can be taken as 25°C and 30°C, respectively.

          • Ceiling height
            The ceiling height shall be based on the height, measured from the finished floor level to the soffit of the ceiling/ roof.

          • Spacing of sprinkler above fire
            Sprinkler spacing shall be based on SS CP 52 (e.g. 3m by 3m or 4m x 3m).

            Note: The application of FPETool from NIST or any other software in determining the activation time of the sprinkler system and the corresponding fire size has its limitations. Some of the software programs are based on Alpert’s correlations where a number of fundamental assumptions are made such as flat smooth ceilings, unconfined smoke flow, axisymmetric plumes (not near walls or corners), location of detector close to the ceiling, etc. Such assumptions shall thus be taken into consideration when using this tool.

        4. The capacity of the smoke control system shall also take into consideration the possibility of forklift or general goods vehicle on fire along the internal ramps/driveways. For design purposes, the design fire size shall be taken as follows:

          TABLE 7.4.5c.(2)(b)(iv) : VEHICLE DESIGN FIRE SIZE

          Type of vehicle

          Design fire size

          Forklift or car

          4MW

          General goods vehicle

          10MW

      3. Determination of perimeter of fire

        1. Fire perimeter for forklift/car and goods vehicle

          The fire perimeter is used to determine the mass flow rate of smoke. For forklift or general goods vehicle, the perimeter of fire shall be taken as follows:

          TABLE 7.4.5c.(2)(C)(I) : FIRE PERIMETER SIZE

          Type of vehicle

          Perimeter of fire

          Forklift or car

          5m x 2m

          General goods vehicle

          9m x 2.5m

        2. Fire perimeter other than for forklift/car and general goods vehicle

          Other than for forklift/car and general goods vehicle, the following equation is used to calculate the fire perimeter for a square fire of equal sides:

          P = 4(Qc/Qr)0.5 -------------------------------- equation (2)
          where:
          P = fire perimeter (m);
          Qc = convective heat output = 0.7Qmax (kW);
          Qr = heat release rate per unit area (kW/m2), see Table 7.4.5c.(2)(c)(ii)

          Where elongated storage configurations such as racking or shelving are used, the fire perimeter is determined using the following equation:

          P = 2[Qc/(Qr x d)] --------------------------- equation (3)
          where:
          Qc = convective heat output = 0.7Qmax (kW);
          Qr = heat release rate per unit area (kW/m2), see Table 7.4.5c.(2)(c)(ii)
          d = depth of rack (m)

          For purpose of calculating the fire perimeter, the values for Qr given in Table 7.4.5c.(2)(c)(ii) are used.

          TABLE 7.4.5c.(2)(C)(II) : HEAT RELEASE RATE

          Building Use

          Heat release rate per unit area, Qr (kW/m2)

          Industrial

          260

          Storage

          500

      4. Capacity

        The capacity of an engineered smoke control system shall be capable of handling the demand for smoke exhaust in a worst case scenario.

Explanations & Illustrations

Clause 7.4.5d. : Engineered smoke control system

Section Figure 7.4.5d. - 1 : Scenario A
Section
Figure 7.4.5d. - 1 : Scenario A
Section Figure 7.4.5d. - 2 : Scenario B
Section
Figure 7.4.5d. - 2 : Scenario B
Section Figure 7.4.5d. - 3 : Scenario C
Section
Figure 7.4.5d. - 3 : Scenario C

The engineered smoke control system can be designed based on smoke control zones, provided the system is capable of handling the largest demand of smoke produced under the worst case scenario. The worst scenario would be scenario C where the fire size occurring at 1st storey as shown in the figure above. As the smoke and hot gases rise through the upper levels, a very large quantity of smoke would be further generated through entrainment and greater cooling effect of smoke would occur.

  1. Clear layer

    The design smoke layer base shall be above the heads of people escaping beneath it. The minimum height shall be 2.5m.

Explanations & Illustrations

Clause 7.4.5e. : Engineered smoke control system

Section Figure 7.4.5e.
Section
Figure 7.4.5e.

The clear height below smoke layer (Y) = 2.5m minimum.

The main purpose is to permit occupants to evacuate in a clear breathable layer. The maintenance of this clear layer will aid the firefighting operations. The lowest  cceptable temperature of smoke layer to prevent loss of buoyancy is 20°C above ambient, i.e. 35°C (or 308K).

The highest temperature to prevent a radiation risk to people passing beneath the smoke layer should not exceed 200°C (or 473K). This temperature may appear high for areas such as means of escape, but it is considered acceptable.

  1. Smoke reservoir

    1. Smoke reservoirs to prevent the lateral spread of smoke, and to collect smoke for removal, shall be of non-combustible construction capable of withstanding smoke temperatures.

Explanations & Illustrations

Clause 7.4.5f.(1) : Engineered smoke control system

Section Figure 7.4.5f.(1)
Section
Figure 7.4.5f.(1)

Smoke reservoirs could be formed by using either the building’s geometry or by using smoke curtains/shutters/non-combustible downstands, such as fire resisting boards, glazing. The screens, which extend downwards from the roof or ceiling to form the smoke reservoir, should preferable be smoke tight. They should be resistant to the effects of the fire. The main reasons for restricting lateral spread of smoke by providing smoke reservoir are:

  1. to prevent damage or even ignition to combustible parts of ceiling lining or service components if hot smoke layers are allowed to spread uncontrolled over unlimited areas; and

  2. to prevent smoke layer (because of mixing with cold air in the course of lateral travel) become relatively cool and shallow. This will result in roof vents being unable to expel the smoke efficiently. Smoke vents would be most effective if the temperature of the smoke layer is high and that the layer beneath the vent is quite deep, thus developing a reasonable pressure differential to act to expel the smoke through the vent.

  1. -

    1. For cases where smoke is removed from the room of origin, the smoke reservoir size for a smoke ventilation system shall not exceed:

      1. 2000m² for a natural smoke ventilation system; and

      2. 2600m² for a mechanical smoke ventilation system.

Explanations & Illustrations

Clause 7.4.5f.(2) : Engineered smoke control system

Section Figure 7.4.5f.(2)
Section
Figure 7.4.5f.(2)

Room of origin includes atria, large shopping floor, rooms or spaces. Large reservoir will present a large surface area to the smoke layer, which can lead to considerable heat losses from it. Smoke control system is therefore designed with maximum specified smoke reservoir size to prevent excessive heat loss from the smoke layer, which leads to loss of its buoyancy for effective smoke venting or exhaust from the building.

  1. -

    1. For cases where smoke is removed from a circulation space or atrium space, the smoke reservoir size for a smoke ventilation system shall not exceed:

      1. 1000m² for a natural smoke ventilation system; and

      2. 1300m² for a mechanical smoke ventilation system.

Explanations & Illustrations

Clause 7.4.5f.(3) : Engineered smoke control system

Section Figure 7.4.5f.(3) - 1 : Smoke extraction from atrium circulation space
Section
Figure 7.4.5f.(3) - 1 : Smoke extraction from atrium circulation space
Figure 7.4.5f.(3) - 2
Figure 7.4.5f.(3) - 2
Elevation A Figure 7.4.5f.(3) - 3
Elevation A
Figure 7.4.5f.(3) - 3

For cases where smoke is allowed to spill into the circulation or atrium space before extraction takes place, the smoke reservoir sizes are halved. Individual smoke reservoir can be created for circulation or atrium space, subject to 1300m² for mechanical ventilation or 1000m² for natural ventilation.

The smoke reservoirs could be formed by using either the building’s geometry or by using smoke curtains/shutters/non-combustible downstands.

The depth of any screen used for subdivision shall be taken into account. Screens should terminate at a minimum of 500mm below the smoke layer base.

The main reasons for limiting the size of reservoirs are:

  1. smoke from a fire leaves a workshop and enters the smoke reservoir in the circulation or atrium space, it will encounter turbulence and greater mixing occurs which produces more smoke; and

  2. the movement of smoke from workshop into the circulation or atrium space would cause the smoke to lose heat to the surrounding structure through conduction and further loss occurring due to downward radiation. This movement would cause the smoke to lose some of its buoyancy.

For factory, the circulation or atrium space serves as a means of escape for people escaping from the workshop, before exiting to a safe area outside the building. The circulation or atrium space is therefore an additional stage to the escape route, which requires to be protected from the effects of fire and smoke.

For warehouse, which is primarily designed for storage, the smoke ventilation system provided would be for the purpose of heat and smoke release from the building. Warehouse should be treated differently from factory.

For warehouse, which is used for palletised storage, consideration should be given to the possible collapse of stacks or radiated heat spreading the fire to adjacent stacks. In tall warehouse, which is used for high rack storage, the smoke layer temperature may not go beyond 35°C and therefore, the smoke layer could well go below the level of the storage. Consideration should be given to the existence of ceiling jet occurring in the smoke layer.

  1. -

    1. Reservoir length

      The maximum length of the smoke reservoir shall not exceed 60m.

Explanations & Illustrations

Clause 7.4.5f.(4) : Engineered smoke control system

Figure 7.4.5f.(4) - 1 : Rectangle-shaped smoke reservoir
Figure 7.4.5f.(4) - 1 : Rectangle-shaped smoke reservoir
Figure 7.4.5f.(4) - 2 : Oval-shaped smoke reservoir
Figure 7.4.5f.(4) - 2 : Oval-shaped smoke reservoir
Figure 7.4.5f.(4) - 3 : Square-shaped smoke reservoir
Figure 7.4.5f.(4) - 3 : Square-shaped smoke reservoir
Figure 7.4.5f.(4) - 4 : Circle-shaped smoke reservoir
Figure 7.4.5f.(4) - 4 : Circle-shaped smoke reservoir
Figure 7.4.5f.(4) - 5 : Rhombus-shaped smoke reservoir
Figure 7.4.5f.(4) - 5 : Rhombus-shaped smoke reservoir

Smoke reservoirs can be formed of different shapes. In order to prevent smoke from excessive heat loss, the length of an individual smoke reservoir within a mall, factory or warehouse spaces shall not exceed 60m.

  1. -

    1. Stagnant regions

      Adequate arrangement(s) shall be made in each smoke reservoir for the removal of smoke in a way that will prevent the formation of stagnant regions.

Explanations & Illustrations

Clause 7.4.5f.(5) : Engineered smoke control system

Section Figure 7.4.5f.(5) - 1
Section
Figure 7.4.5f.(5) - 1

A stagnant region occurred in a long smoke reservoir when venting or extraction is not properly distributed or when circulation/atrium or mall has a closed end.

Section Figure 7.4.5f.(5) - 2
Section
Figure 7.4.5f.(5) - 2

A stagnant region could also be formed by physical obstruction in the smoke reservoir e.g. Beam. If a smoke layer is stagnant, it will cool down and will mix into the air below. If the air space under a smoke layer is stagnant, it will tend to fill up with hazy smoke of sufficient density to affect visibility. Venting or extraction should be well distributed in the smoke layer or smoke reservoir. The air inlets at low level should also be well distributed so that the air, which is being drawn in will purge as much of the low-level clear air as possible.

  1. -

    1. Perforated ceiling

      For cases where the smoke reservoir is above the false ceiling, the ceiling shall be of perforated type with at least 25% opening.

Explanations & Illustrations

Clause 7.4.5f.(6) : Engineered smoke control system

Section Figure 7.4.5f.(6)
Section
Figure 7.4.5f.(6)

If the smoke reservoir incorporates a false ceiling, then the space above the false ceiling may be included in the depth of the smoke reservoir provided the screens forming the reservoir extend up to the structural ceiling, the perforations in the false ceiling are at least 25% of the total area of the reservoir, and the space occupied by services etc. above the ceiling is not greater than 50% of the volume above the ceiling.

  1. Discharge of smoke

    1. Removal of smoke

      For cases where smoke is removed from a circulation space or atrium space, the rooms discharging smoke into the circulation space/atrium spaces shall either:

      1. have a floor area of not exceeding 1000m² (for natural ventilation system) or 1300m² (for mechanical ventilation system), or

      2. be subdivided such that smoke is vented to the circulation space or atrium only from part of the room with floor area not exceeding 1000m² (for natural ventilation system) or 1300m² (for mechanical ventilation system), that is adjacent to the circulation space or atrium. However, the remainder of the room needs to be provided with an independent smoke ventilation system(s).

Explanations & Illustrations

Clause 7.4.5g.(1) : Engineered smoke control system

Figure 7.4.5g.(1) - 1
Figure 7.4.5g.(1) - 1

The main purpose of controlling the max. floor area is to limit the distance to the circulation or atrium space as smoke and hot gases would tend to cool and lose its buoyancy if floor area becomes larger.

Where the workshop units are not larger than 1000m² (natural ventilation in the circulation or atrium space) or 1300m² (with powered extraction in the circulation or atrium space), smoke from these units are allowed to discharge into the circulation or atrium space. If the units are larger than the sizes mentioned above, the smoke layer from a fire in any of these units would lose temperature to a great extent thereby losing its buoyancy as it would be controlled by sprinklers located within the units. In addition, the smoke layer would also lose some heat to the building structures. Thus, the venting of smoke layer into the circulation or atrium space becomes not effective, as cooling of smoke takes place leading to dispersal of smoke and smoke logging.

Figure 7.4.5g.(1) - 2
Figure 7.4.5g.(1) - 2

The combined floor area of multiple shops should not exceed 1000mor 1300m2 (power extraction) fronting circulation or atrium space. It is acceptable to use screen to channel the smoke from the shop into the circulation or atrium space, subject to maximum 14m separation between channel screens.

  1. -

    1. Exhaust points

      The minimum number and siting of exhaust points within a smoke reservoir shall be determined to prevent “plug-holing” effect at the exhaust points. The exhaust point shall comply with the following plugholing equation.

      Figure 7.4.5g.2
      Figure 7.4.5g.2

Explanations & Illustrations

Clause 7.4.5g.(2) : Engineered smoke control system

Figure 7.4.5g.(2)
Figure 7.4.5g.(2)

Where a large workshop is extracted separately from the circulation/atrium space, it can have ceiling reservoirs up to twice the area permitted in the circulation/atrium space; 2000m² (natural ventilation system) or 2600m² (mechanical ventilation system) as no smoke is allowed to spill into the circulation/atrium space.

  1. Limitations

    Owing to practical limitations, a smoke ventilation system shall have:

    1. a maximum mass flow not exceeding 175kg/s; and

    2. a minimum smoke layer temperature of 18°C above ambient temperature.

Explanations & Illustrations

Clause 7.4.5h. : Engineered smoke control system

  1. It has commonly been found that very large exhaust rates, typically larger than about 175 kg/s, become impractical as large and heavy fans or ventilators would be required. Large and heavy fans or ventilators required additional structural supports.

  2. A minimum design temperature is required to maintain stability of the smoke layer. Smoke layers which have temperatures approaching that of the replacement air will have a tendency to mix with this air rather than to float above it.

    The stipulated minimum design layer temperature is intended to be high enough to allow safe operation of the system for fires which are smaller than the full design size.

  1. Replacement air

    1. Replacement air shall by natural means be drawn directly from the external space.

    2. The design replacement air discharge velocity shall not exceed 5m/s to prevent the escapees being hindered by the air flow.

    3. Replacement air intake shall be sited at least 5m away from any exhaust air discharge.

    4. Replacement air shall be discharged at a low level, at least 1.5m beneath the designed smoke layer, to prevent fogging up of the lower clear zone.

    5. Where the inlet cannot be sited at least 1.5m below the smoke layer, a smoke curtain or a barrier shall be used to prevent replacement air disrupting the smoke layer.

    6. Where replacement air is taken through inlet air ventilators or door- ways, devices shall be incorporated to automatically open such inlet ventilators and doors to admit replacement air upon activation of the smoke ventilation system.

    7. Where the roller shutters are used as replacement air inlets in the design and installation of an engineered smoke control system or smoke purging system, they shall be of perforated type, having the required effective free area for the effective operation of the engineered smoke control system. Non-perforated type of roller shutters with solid surface shall not be used.

Explanations & Illustrations

Clause 7.4.5i. : Engineered smoke control system

Section Figure 7.4.5i. - 1
Section
Figure 7.4.5i. - 1

The use of fan-driven inlet air supply can give problems with mechanical extraction. This is because the warmed air taken out will have a greater volume than the inlet air. As the fire grows and declines, the mismatch in volume between the inlet air and the extracted fire warmed air will also change. This can result in significant pressure differences appearing across any doors on the escape routes. Hence, to avoid this “push-pull” effect, replacement air shall be drawn by natural means.

Section Figure 7.4.5i. - 2
Section
Figure 7.4.5i. - 2

A moving airstream in contact with a region of stationary air (or smoke, or gas) will have a lower pressure than the stationary air – this is the Venturi effect. Hence, a moving airstream will attract the stationary air towards itself. The force of attraction increases with increasing velocity of the airstream. In Figure 7.4.5i – 2, the clean airstream flowing through the door attracts the smoke towards itself. The smoke reservoir base follows the surface of constant pressure, and bulges downwards near the door. Unless the reservoir base is high enough above the door (at least 1.5m), the smoke base will come just below the top of the door.

Section Figure 7.4.5i. - 3
Section
Figure 7.4.5i. - 3

Where inlets (e.g. door) cannot be sited at least 1.5m below the base of smoke layer, either a smoke curtain or a horizontal shelf could be used to prevent inlet air distorting the smoke layer. Figure 7.4.5i. – 3 shows a smoke-restraining curtain set back from the door. The curtain’s bottom edge is higher than the door. The incoming air stream will increase in vertical section as it travels from the door to beneath the curtain, and so will slow down. There are fewer tendencies to pull down the smoke base. There is less turbulence at the smoke/air interface mixing smoke into the air stream and any such mixed smoke is at a higher level. The curtain shall be more than 3m away from the door.

Section Figure 7.4.5i. - 4
Section
Figure 7.4.5i. - 4

Using a horizontal shelf instead of a smoke curtain, which permits the same air expansion and gives the same results. The shelf-edge should be more than 3m away from the door.

  1. Emergency power supply

    The engineered smoke ventilation system shall be provided with secondary source of power supply.

Explanations & Illustrations

Clause 7.4.5j. : Engineered smoke control system

All the associated systems/mechanisms, like the door venting actuators, are to be back-up by secondary power supply. This is necessary, as these devices are not incorporated with “standby” batteries that can operate the mechanisms to function as required in the emergency mode.

  1. Mode of activation

    1. Automatic activation

      1. The engineered smoke ventilation system shall be activated by smoke detectors located in the smoke control zone. Use of smoke detectors for activation shall be carefully designed, so that accidental or premature activation of smoke detectors in a non- fire zone (due to smoke spills or spread from other areas) are avoided.

      2. Provision of activating smoke detectors shall comply with SS 645.

    2. Manual activation

      A remote manual activation and control switches, as well as visual indication of the operation status of the smoke ventilation system, shall also be provided at the FCC. Where there is no FCC, it shall be indicated at the main fire alarm panel.

Explanations & Illustrations

Clause 7.4.5k.(1)(a) : Engineered smoke control system

Section Figure 7.4.5k.(1)(a)
Section
Figure 7.4.5k.(1)(a)

Scenario A :

A fire occurring at 3rd storey failed to activate the smoke detector at that level owing to its poor location. Instead, smoke is allowed to spill into the atrium void and smoke control system for the building is activated. This would release all the smoke curtains overlooking the atrium void, including the fire floor, which is not correct. As a result, smoke and heat will be retained in the fire floor. The correct sequence of events should be that the smoke detectors at the fire floor should be activated first, thereby locking the smoke curtain, while releasing all smoke curtains in other parts of the building.

Scenario B :

A fire occurring at the atrium floor caused smoke to spill and activate the smoke detector in 2nd storey. The smoke
curtain will remain locked but at other floors, the smoke curtains will descend down. As a result, part of 2nd storey will be smoke logged.

Smoke control system reacts to the first signal sent by the detector. To overcome the above problem, it is recommended that closer spacing of smoke detectors, closer than the permitted limit in SS CP 10, be adopted and that the detectors should be placed correctly in close proximity of the atrium void.

Clause 7.4.5k.(1)(b) : Engineered smoke control system

The smoke ventilation system shall operate automatically upon detection of smoke by smoke detector placed strategically at the smoke control zone. The layout of smoke detectors shall comply with SS CP 10.

Rationale

Clause 7.4.5k.(2)

The provision of remote manual activation and control switches located at Fire Command Centre or Fire Alarm Panel would permit better controlling of the smoke ventilation system.

In the event of the smoke detectors malfunctioning, the atrium smoke extract system can be activated by a manual switch, which performs the function of the smoke detectors in actuating the associated devices for the isolation and extraction of the smoke from the affected areas.

  1. Interlocking with other ACMV systems

    Except for ventilation systems in Cl.5.2.1g. and  Cl.5.2.1h., all other air-conditioning and mechanical ventilation systems within the areas served shall be shut down automatically upon activation of the smoke ventilation system.

Explanations & Illustrations

Clause 7.4.5l. : Engineered smoke control system

Mechanical ventilation to the following room or space should not be affected:

  1. exit staircases and exit passageways;

  2. smoke-stop and fire lift lobbies;

  3. areas of refuge within the same building;

  4. basement car parks;

  5. fire command centres;

  6. flammable liquid/gas storage room;

  7. emergency generator; and

  8. engine driven fire pump.

AHUs serving the affected smoke zone are to be shut down automatically upon activation of the smoke ventilation system, while the rest may continue to function.

  1. Standby fans/ multiple fans

    1. Either a standby fan or multiple fans with excess capacity shall be provided for each mechanical smoke ventilation system, such that in the event the duty fan or the largest capacity fan fails, the required smoke extraction rate will still be met. The standby fan shall be automatically activated in the event the duty fan fails.

    2. Fans shall be capable of operating at 250°C for 2 hours.

    3. Protected circuits

      The fans and associated smoke control equipment shall be wired in protected circuits designed to ensure continued operation in the event of fire.

    4. Electrical supply

      The electrical supply to the fans shall, in each case, be connected to a sub-main circuit exclusive thereto after the main isolator of the building. The cables shall be of at least 1-hr fire resistance rating in accordance with SS 299.

Explanations & Illustrations

Clause 7.4.5m.(1) : Engineered smoke control system

Section Figure 7.4.5m.(1)
Section
Figure 7.4.5m.(1)

Rationale

Clause 7.4.5m.(3)

Since the smoke control system is installed to remove smoke and heat from the building to aid evacuation of occupants and firefighting operations, the system’s circuits shall be protected to ensure operational reliability and sustained operation during fire emergency.

Clause 7.4.5m.(4)

The main purpose is to ensure that the electrical supply to the fans could be maintained continuously for at least 1 hour.

  1. Smoke ventilation ducts

    1. Smoke ventilation ducts (both exhaust and replacement air ducts) shall be of at least 1-hr fire resistance rating. The rating shall apply to fire exposure from both the interior and exterior of the duct or structure and the duct shall also comply with Cl.7.1.2h..

    2. Where a duct passes through another fire compartment with higher fire rating, the duct shall be constructed to have fire-rating as that of the compartment. Where a duct is installed in a single fire compartment and does not pass through another compartment, smoke control ducts (both exhaust and replacement air ducts) within that compartment need not comply with the 1-hr fire resistance rating requirement subject to the following conditions:

      1. the smoke ventilation ducts (both exhaust and replacement air ducts) are constructed of at least 1.2mm thick galvanised steel sheet;

      2. sprinklers, designed to SS CP 52, shall be provided above and below the entire length of the ducts (regardless of the duct dimensions) to protect the duct surfaces from the effect of water spray through the activated sprinklers; and

      3. the construction and support of the duct shall conform to the appropriate requirements of the duct construction standards contained in ASHRAE Handbook, IHVE Guild books or SMACNA Manuals.

  1. Fire damper

    1. Fire dampers shall not be fitted in the smoke ventilation system, except where used in an engineered smoke control system. In such a situation, the fire-smoke dampers shall be constructed in accordance with SS 333.

    2. The damper shall be in closed position during fail-safe mode.

    3. The combination fire and smoke damper, and any duct extension between it and the protected vent shaft, shall be of the same rating as the element of structure.

    4. Sprinkler protection shall be provided to the electric actuator.

    5. The electrical power supply cables to the electric actuator shall be fire resistant.

  2. Time taken

    The time for a smoke ventilation system within a smoke zone to be fully operational shall not exceed 60 secs from the time of activation.

  3. Natural ventilation

    Natural ventilation shall not be used together with mechanical ventilation.

  4. Smoke curtain

    All smoke curtains, where required, unless permanently fixed in-position, shall be brought into position automatically to provide adequate smoke-tightness and effective depth.

Explanations & Illustrations

Clause 7.4.5q. : Engineered smoke control system

Section Figure 7.4.5q.
Section
Figure 7.4.5q.

Wrong positioning of roof ventilators can cause the wind to be deflected into the atrium roof space, thereby pushing the smoke downward into the building. Roof adjacent to tall buildings could be subjected to positive pressure. It is for the designer to prove that his design will be satisfactory.

Clause 7.4.5r. : Engineered smoke control system

Section Figure 7.4.5r.
Section
Figure 7.4.5r.

The combination of natural exhaust ventilation and powered smoke exhaust ventilation in a building would create complications on the design of the distance between the bottom of the smoke reservoir and the floor and also the extent of the depth of the smoke reservoir.

  1. Obstruction to means of escape

    A smoke curtain, or other smoke barrier, located at any access route forming part of or leading to a means of escape, shall not in its operational position obstruct said escape route.

Rationale

Clause 7.4.5s

The intent of the smoke curtain is to contain the smoke and to prevent spillage of smoke to other areas.

  1. Smoke or chanelling screens

    Where glass walls or panels are being used as smoke screens to form a smoke reservoir or as channelling screens, they shall be able to withstand the design highest temperature.

Explanations & Illustrations

Clause 7.4.5t. : Engineered smoke control system

Section Figure 7.4.5t.
Section
Figure 7.4.5t.

Upon activation of smoke detector, the smoke curtain is automatically unfurled from its roller under gravity fall to impede smoke flow. The dropped curtains limit the area of smoke spread, maintain visibility and tenable conditions for escape purposes.

Smoke curtain in operation should not obstruct the escape routes. The clear height of smoke curtain across the escape routes should not be lower than 1.8m from its finished floor level.

  1. Smoke control equipment

    All smoke control equipment (including smoke curtains) shall be supplied and installed in accordance with BS EN 12101-1, BS EN 12101-3 and BS 7346 Part 7 or equivalent.

  2. Engineered smoke control system

    Fixed screen shall be constructed of non-combustible materials capable of resisting the highest design temperatures. Automatic retractable smoke curtains are required to comply with BS 7346 and listed under Product Listing Scheme.

Explanations & Illustrations

Clause 7.4.5u. : Engineered smoke control system

Figure 7.4.5u. - 1
Figure 7.4.5u. - 1

Wired glass or tempered glass could be used as smoke screen to form smoke reservoir, provided they are able to meet the designed highest temperature. Glass walls or panels acting as smoke screen shall not be of sliding, louvers or openable type.

Section Figure 7.4.5u. - 2
Section
Figure 7.4.5u. - 2

Smoke screens, which are to meet the designed highest temperature, could be used to form smoke reservoirs to limit lateral spread. Smoke channelling screens are used to channel smoke away from the origin of fire to smoke reservoirs where extraction can be carried out, or away from the building entrance canopies to the external open space as shown above.

It is recommended that the spacing between channelling screens should not be more than 14m so as to prevent lateral spread of smoke and excessive cooling.

7.4.6

Fail-safe system

For natural smoke ventilation system, the natural ventilators shall be-

  1. in the “open” position in the event of power/system failure; and

  2. positioned such that they will not be adversely affected by positive wind pressure.

    Note: Natural ventilators refer to any device e.g., entrance sliding doors or any other mechanised openings for fresh air replacement or smoke venting to external space.

7.5

Redundancy for Mechanical Ventilation and Pressurisation Systems

7.5.1

Provision

  1. Powered system

    A standby fan (N+1) shall be provided for each of the following systems, such that in the event one of the duty fans fails or taken out of service, the standby fan shall be automatically activated to meet the required ventilation rate. 

    1. mechanical ventilation systems for: 

      1. smoke-free/ fire lift lobbies;

      2. exit staircases; and

      3. essential rooms (e.g., sprinkler/ wet riser/ hydrant/ hose  reel pump room, standby generator room, FCC, etc.).

    2. engineered smoke control systems; 

    3. car park smoke purging systems*; and 

    4. pressurisation systems for smoke-free/ fire lift lobbies, exit staircase and hotel internal guestroom corridor.

      Note * redundancy (N+1) achieved by having at least 2 zones for ductless system in operation, in which N+1 fans for each zone is not required. 

  2. Non-powered system
    Where automatic smoke ventilators are used as part of the smoke control system, there shall be at least 10% redundancy on the quantities of ventilators and shall be located such that they are not affected by the wind. The quantity of the redundant ventilators shall be round up to whole numbers, based on the largest size of the ventilators used.

Diagram 7.1.13c.(1) - 1 : Unprotected opening perpendicular to the kitchen exhaust duct

Diagram 7.1.13c.(1) - 1 : Unprotected opening perpendicular to the kitchen exhaust duct
Diagram 7.1.13c.(1) - 1 : Unprotected opening perpendicular to the kitchen exhaust duct

Diagram 7.1.13c.(1) - 2 : Unprotected opening parallel to the kitchen exhaust duct

Diagram 7.1.13c.(1) - 2 : Unprotected opening parallel to the kitchen exhaust duct
Diagram 7.1.13c.(1) - 2 : Unprotected opening parallel to the kitchen exhaust duct

Diagram 7.1.13c.(2) : Fire resistance construction for kitchen exhaust duct

Diagram 7.1.13c.(2) : Fire resistance construction for kitchen exhaust duct
Diagram 7.1.13c.(2) : Fire resistance construction for kitchen exhaust duct

Diagram 7.1.13c.(3) : Installation of non-fire-rated kitchen exhaust duct above LPG cylinders

Diagram 7.1.13c.(3) : Installation of non-fire-rated kitchen exhaust duct above LPG cylinders
Diagram 7.1.13c.(3) : Installation of non-fire-rated kitchen exhaust duct above LPG cylinders

Diagram 7.1.13c.(4) : Installation of non-fire-rated kitchen exhaust duct in close proximity to LPG cylinders and vapouriser

Diagram 7.1.13c.(4) : Installation of non-fire-rated kitchen exhaust duct in close proximity to LPG cylinders and vapouriser
Diagram 7.1.13c.(4) : Installation of non-fire-rated kitchen exhaust duct in close proximity to LPG cylinders and vapouriser

Diagram 7.4.4e.(4) - 1 & 2 : Wiring arrangement of jet fan system

Diagram 7.4.4e.(4) - 1 : Wiring arrangement of jet fan system
Diagram 7.4.4e.(4) - 1 : Wiring arrangement of jet fan system
Diagram 7.4.4e.(4) - 2 : Wiring arrangement of jet fan system
Diagram 7.4.4e.(4) - 2 : Wiring arrangement of jet fan system