Criteria Ref | Current Code for Environmental Sustainability of Buildings (3rd Edition) and Approved Document | Criteria Ref | Requirements to be incorporated in upcoming Code for Environmental Sustainability of Buildings (4th Edition) |
|---|
| General The minimum Green Mark Score of 50 points and the stipulated pre-requisite requirements The criteria comprise 5 environmental impact categories namely Part 1 – Energy Efficiency Part 2 – Water Efficiency Part 3 – Environmental Protection Part 4 – Indoor Environmental Quality Part 5 – Other Green Features The score is the total of all the numerical scores assigned based on the degree of compliance with the applicable criteria listed under the 5 categories. | | General The environmental sustainability compliance framework was simplified and streamlined to complement the sustainability requirements regulated by other agencies. It is broadly grouped into two sections namely the Base Requirements and Carbon reduction measures. The Base Requirements will cover sustainability indicators relating to passive and active strategies, which have a direct impact on building energy efficiency standards and are mandatory, where applicable. The section on Carbon Reduction Measures covers sustainability indicators that will help drive a low carbon future by way of sustainable design, construction practices and technologies. The minimum environmental sustainability standard shall have a level of environmental performance that meets all relevant base requirements and a selected number of sustainability indicators provided under Carbon Reduction Measures in order to meet 50 points as required. The Carbon Reduction Measures are broadly grouped in 3 Sections namely Section 1 – Sustainable Design Strategies Section 2 – Sustainable Construction Section 3 – Sustainable Technologies In summary, Residential Buildings | Non-Residential Buildings |
|---|
All Base Requirements listed in Table 4.1(a), where applicable. A selection of four (4) Carbon Reduction Measures in total as listed in Table 4.2(a) including a minimum of two (2) measures from Section 2 - Sustainable Construction.
| All Base Requirements, listed in Table 4.1(b), where applicable. A selection of four (4) Carbon Reduction Measures in total as listed in Table 4.2(b) including a minimum of two (2) measures from Section 2 - Sustainable Construction.
|
For building works that involve only the erection of simple structures and buildings that are solely use for special functions only the Base Requirements will be applicable. Examples, link ways, underground passes, open sheds, standalone substation, lift upgrading, farm structures, temporary workers’ dormitories, treatment plants, transport facilities. However, note that this does not apply to building works that form part of the residential and non-residential building developments. |
For Residential Building Development |
|---|
Part 1 – Energy Efficiency | Part 1 – Base Requirements |
RB1-1 | Thermal Performance of building Envelope (RETV) Based on every reduction of 1W/m2 from baseline of 25 W/m2 Note that under Approved Document – Maximum permissible RETV is 25 W/m2 . | RB 01 | Envelope and Roof Thermal Transfer Maximum permissible RETV will be 22 W/m2 in accordance with the methodology stated under the Code on Envelope Thermal Performance of Buildings Note: This requirement is enhanced to further reduce heat gain thru’ building envelope The building envelope designed is deemed to have satisfied the performance requirement if it meets the following criteria Window to Wall Ratio (WWR) | Shading Coefficients of Glass (SCglass) |
|---|
< 0.30 | ≤ 0.67 | 0.30 to < 0.35 | ≤ 0.59 | 0.35 to < 0.40 | ≤ 0.52 | 0.40 to < 0.45 | ≤ 0.48 | 0.45 to ≤ 0.50 | ≤ 0.43 |
|
RB 1-2 (a) (ii) | Provision of air-conditioning system Based on provision of air-conditioning system with 3 ticks or 4 ticks rating for 80% of total number of dwelling units. | RB02-1 | Air-Conditioning System Minimum 5-tick or 3-tick rated based on type of air-conditioners for 80% of total number of dwelling units and common facilities. Minimum Energy Performance Standard |
|---|
Single/ Multi Spilt System | 5-tick rated | Variable Refrigerant Flow (VRF) system | 3-tick rated |
|
RB 1-4 | Artificial lighting Based on percentage improvement over maximum lighting power budget stated in SS 530 | RB 02-2 | Lighting System for Common Areas and Facilities Minimum 40% improvement over maximum lighting power budget stated in SS 530 |
RB1-5 | Ventilation in Car parks Based on mode of ventilation – NV, MV with and without fume extracts – with CO sensors | RB 02-3 | Mechanical Ventilation System in Car parks MV car parks – to be equipped with CO sensor control with VSDs |
Part 1 – Energy Efficiency | Part 2 – Carbon Reduction Measures – Sustainable Design Strategies |
RB 1-1 | Thermal Performance of Building Envelope Based on every reduction of 1W/m2 from baseline of 25 W/m2 | RBE01-1 | Enhanced Building Envelope Performance RETV of not more than 20 W/m2 Application of cool materials on external wall or roof areas provision of innovative façade technology
|
RB 1-2 | Naturally Ventilated Design Based on extent of coverage in the following areas Ventilation Simulation Modelling and Analysis OR Ventilation Design - Building layout design & Dwelling unit design Naturally Ventilated in common areas
| RBE01-2 | Naturally Ventilated Building Design Building layout design with 30% of all units with prevailing wind condition Dwelling unit design with 25% of habitable spaces with good cross ventilation Passive design considerations for dwelling unit indoor comfort and design for natural ventilation with minimum coverage of 80% in at least two(2) of the following areas
|
RB 1-3 | Daylighting Based on extent of coverage via Daylight and Glare simulation analysis for dwelling units Daylight for common areas
| RBE01-3 | Effective Daylighting Habitable Spaces : Daylighting provision for 25% of the total number of residential units that meets the desired lighting level of DA200lx, 50% in 60% of applicable areas (namely bedrooms, living room, family room and study room) based on daylight availability table provided. Non-Habitable Spaces: Provision of daylighting with minimum coverage of 80% in at least two (2) of the following areas :
Note: No daylight simulation required for item (a) |
Part 3 - Environmental Protection | Part 2 – Carbon Reduction Measures – Sustainable Construction (at least two measures) |
RB3-1 | Sustainable Construction Concrete Usage Index (CUI)
Encourage designs with efficient use of concrete for building components – Points accorded for a range of CUI from 0.7 to 0.35 | RBE02-1 | Resource Efficiency Measures Existing building structures with more than 50% of the floor and/or wall areas conserved for adaptive reuse. Design with Concrete Usage Index (CUI) of not more than 0.48. Embodied carbon reporting to account for the upfront carbon emissions of three (3) key construction materials namely, concrete, steel, and glass used in building developments.
Note: Item (a) is similar to the requirement under Green Features and Innovation of Current Code. Item (b) – the methodology will be the same as current Code with a low CUI stipulated to encourage efficient concrete usage Item (c) – A new requirement incorporated to encourage carbon accounting for three key construction materials
|
| 3-1 (a) Based on extent of use for (a) green cements (b) Recycled concrete aggregate (RCA) (c) Washed Copper Slag (WCS) | RBE02-2 | Low Carbon Concrete Enhance carbon reduction with the use of following sustainable materials in building construction. Use of concrete with eco-friendly cementitious materials that are classified under CEM II to V types for at least 80% of the super structural works by volume. Use of recycled concrete aggregate (RCA) and/or washed copper slag (WCS) from approved sources that meet the minimum usage requirement (that is 1.5% x GFA for RCA and/or 0.75 x GFA for WCS) Alternative construction materials that can be used as a replacement for standard building materials for non-structural application.
Note : These requirements are generally similar to current Code but are enhanced with stipulated standard and have included new materials for construction such as granite fines. |
RB3-2 | Sustainable Products Based on extent of coverage, environmentally friendliness, areas of application. Minimum 1 tick rated (Good) from an approved local product certification body | RBE02-3 | Sustainable Products Minimum three (3) sustainable products with EPDs or minimum 2 ticks (Very good) rated from an approved local product certification body Note : This requirement is enhanced to encourage the use of building products with lower embodied carbon. Only products with EPDs or minimum 2 tick rating can be considered. |
Part 1 - Energy Efficiency | Part 3 – Carbon Reduction Measures – Sustainable Technologies |
RB1-8 | Renewable Energy Based on extent of provision with minimum 1 % replacement (exclude household’s usage) | RBE03-1 | Renewable Energy System Recognition given for on-site renewable energy systems with a minimum capacity installation of 15% roof coverage of the residential blocks within the development. Note : This requirement is enhanced to consider spatial requirement which is more direct in assessing the potential to adopt PV system. The placement of the system is not restricted to roof space of residential blocks to provide flexibility in design. |
| No mention | RBE 03-2 | Smart Technology Solutions Recognition given to the adoption of smart solutions and technologies which help facilitate resource usage monitoring and reduce overall energy consumption. Examples of solutions or technologies that can be considered are as follows : Energy dashboard, web-based or mobile application or equivalent to provide useful and timely information on utilities consumption and breakdown for homeowners and/or facility manager Energy recovery system Lifts with regenerative function Occupancy sensors/controls for lighting in private lift lobbies, staircases or common facilities Others (to be evaluated on a case-to-case basis)
|
For Non-Residential Building Development |
Part 1 – Energy Efficiency | Part 1 – Base Requirements |
NRB1-1 | Thermal Performance of building Envelope (ETTV) Based on every reduction of 1W/m2 from baseline of 50 W/m2 Note that under Approved Document – Maximum permissible ETTV is 50 W/m2 . | NRB01 | Envelope and Roof Thermal Transfer Maximum permissible ETTV will be 45 W/m2 in accordance with the methodology stated under the Code on Envelope Thermal Performance of Buildings The building envelope designed is deemed to have satisfied the performance requirement if it meets the following criteria Window to Wall Ratio (WWR) | Shading Coefficients of Glass (SCglass) |
|---|
< 0.20 | ≤ 0.51 | 0.20 to < 0.25 | ≤ 0.41 | 0.25 to < 0.30 | ≤ 0.35 | 0.30 to < 0.35 | ≤ 0.30 | 0.35 to < 0.40 | ≤ 0.27 | 0.40 to ≤ 0.50 | ≤ 0.22 |
|
| Source : Approved Document Roof with skylight : Maximum permissible RTTV is 50 W/m2 in accordance with the methodology stated under the Code on Envelope Thermal Performance of Buildings Roof without skylight Roof Weight Group | Weight Range (kg/m2) | Maximum U- value (W/m2k) |
|---|
Light | <50 | 0.5 | Medium | 50 to 230 | 0.8 | Heavy | >230 | 1.2(air-con) 1.5 (non air-con) |
| NRB01-2 | Roof Roof with skylight : Maximum permissible RTTV at 50 W/m2 in accordance with the methodology stated under the Code on Envelope Thermal Performance of Buildings Roof without skylight Roof Weight Group | Weight Range (kg/m2) | Maximum U- value (W/m2k) |
|---|
Light | <50 | 0.5 | Medium | 50 to 230 | 0.8 | Heavy | >230 | 1.2 |
|
| Source : Approved Document I.3.4. Air-Tightness and Leakage All windows on the building envelope shall not exceed the air leakage rates specified in SS 212 Where the door opening of any commercial unit is located along the perimeter of the building envelope, that unit shall be completely separated from the other parts of the buildings and has its air-conditioning system separated from and independent of the central system
| NRB02 | Air-Tightness and Leakage All windows and curtain walls shall be designed to ensure that the airleakage rates do not exceed the limits specified in SS 212 and SS654 respectively Building entrances and door openings to building exterior or non air conditioned spaces and the like, shall be provided with doors that are equipped with automated technology or self-closing devices. Where door opening of any commercial units are located along the perimeter of the building envelope, that unit shall be equipped with addition of pressure independent control valve and energy meter to measure the consumption of fan coiled units (FCUs) within the unit; and be equipped with enclosed vestibules or other appropriate measures for doorway with high pedestrian traffic flow*. In the case of vestibules, the interior door and exterior door must have a minimum distance of not less than 2.5 m apart and should be interlocked to avoid being opened at the same time.
* Doorway with high pedestrian traffic flow refers to main entrances and those leading to transport nodes or other commercial buildings |
| Note : Compliance with specific energy savings requirement and approach using energy modelling simulation are not included in current Code | NRB03 | Building Energy Performance The compliance with the energy performance that meet minimum energy improvements of 50% over 2005 baseline by way of energy modelling simulation OR the respective performance standards set out below. |
NRB03-1 | Whole building approach via Energy Modelling Demonstration of energy saving requirements 30% over prevailing Singapore Standard and baseline based on Energy Modelling Methodology and requirements. The limits set for Total System Efficiency (TSE) of respective building cooling system shall apply.
|
NRB 1-2 | Air Conditioning System Water-Cooled Chilled-Water Plant :
Water-Cooled Chiller Chilled-Water Pump Condenser Water Pump Cooling Tower
Baseline | Peak Building Cooling Load |
|---|
≥ 500 RT | < 500 RT | Prerequisite Requirements Minimum Design System Efficiency (DSE) for central chilled-water plant | 0.70 kW/RT | 0.80 kW/RT |
Air-Cooled Chilled-Water Plant /Unitary Air-Conditioners
Baseline | Peak Building Cooling Load |
|---|
≥ 500 RT | < 500 RT | Prerequisite Requirements Minimum Design System Efficiency (DSE) for air cooled chilled-water plant or unitary conditioners | 0.80 kW/RT | 0.90 kW/RT |
| NRB03- 2(a) | Air-Conditioning System Water-Cooled Building Cooling System
Water-Cooled Chiller; Chilled-Water Pump; Condenser Water Pump; Cooling Tower; and Air-Distribution System
Total System Efficiency (TSE) for Water-Cooled Building Cooling System |
|---|
New Buildings | Existing Buildings with New Extension and Major Retrofits | 0.85 kW/RT | 0.9 kW/RT |
Air-Cooled Building Cooling System
Unitary Air-Conditioners (Single or combination of systems) Variable Refrigerant Flow (VRF) system Single – Spilt Units Multi-Spilt Units Air-Distribution System Air-Cooled Chilled-Water System can be adopted in relation to existing building development with inherent constraints and with peak building cooling load of not more than 500 RT Air-Cooled Chiller Chilled Water Pump Air-Distribution System
Total System Efficiency (TSE) for Air-Cooled Building Cooling System |
|---|
New and Existing Buildings with New Extension or Major Retrofits | 1.0 kW/RT |
where TSE refers to the combined design system efficiency of the chiller plant or condenser units and air-distribution systems. Note (1) Unlike the current Code, the minimum energy performance standard is pegged based on the Total Design System Efficiency which comprises both the water-side system and air-side system efficiency. In other words, it is a requirement to consider the air-distribution system efficiency in meeting the TSE. Noted that there will be minimum standards required for water cooled chilled water plant, air-cooled chilled water plant and unitary air conditioners – condensers and as follows : Water-Cooled Building Cooling System Minimum Water-Cooled Chilled Water Plant Efficiency ηc |
|---|
New Commercial Buildings | Other Building Developments | Chilled Water Supply Temp (˚C) | 6 | 7 | 8 | 9 | 10 | For chilled water supply temp above 10˚C, the threshold will be adjusted from 0.64 kW/RT by 0.01 kW/RT for every 1˚C increase in chilled water supply temperature | 0.63 kW/RT | Water-Cooled Chiller System Efficiency (kW/RT) | 0.68 | 0.67 | 0.66 | 0.65 | 0.64 |
For buildings with cooling provision that tap on District Cooling System (DCS), the TSE requirement does not apply but the air-distribution system efficiency must meet the minimum energy performance standard of 0.25 kW/RT. Air- Cooled Building Cooling System Minimum Air-Conditioning System Efficiency ƞc |
|---|
Unitary System (Outdoor Condenser Units) | Air-Cooled Chilled Water Plant | All Buildings | Applicable to only Existing Buildings with New Extension or Major Retrofits | 0.78 kW/RT (inclusive site deration factor) | 0.85 kW/RT |
The provision of air-cooled chilled water plant can only be considered for existing buildings with new extension or major retrofits. Note (2) The air-distribution system efficiency can be adjusted to allow for pressure drop adjustments for fan system where there is a need for more allowance due to functionality and activities as per recommended by SS 553 – Table 2b. Note(3) Where there is a combination of water cooled and air-cooled building cooling system, the respective TSEs are to be complied with. |
NRB 1-4 RB 1-4 | Artificial Lighting Based on percentage improvement over maximum lighting power budget stated in SS 530 | NRB01 -2(b) RB01-2 | Lighting System The lighting provision shall be at least 40% more energy efficient than the prescribed lighting power budget stated in SS 530 – Code of Practice for Energy Efficiency Standard for Building Services and Equipment. |
NRB 1-4 (b) | Mechanical Ventilation Based on percentage improvement in mechanical ventilation system efficiency over the baseline stipulated in SS 553. | NRB01 -2(c) | Mechanical Ventilation System Provision of mechanical ventilation system of at least 10% more energy efficient than the prescribed standard stated in SS 553 for normally occupied spaces that utilise mechanical ventilation as the preferred ventilation mode. Provision of CO detection sensor control with VSD to regulate demand for mechanical ventilation in car parks Note : There is a minimum energy improvement of 10% over baseline stipulated in SS 553 which is applicable only to the normally occupied spaces and car parks. |
| Measurement and Instrumentation Requirements for water cooled chilled water air conditioning system Prerequisite Requirements : Provision of permanent measuring instruments for monitoring of water-cooled chilled-water plant efficiency. The installed instrumentation shall have the capability to calculate a resultant plant efficiency (i.e. kW/RT) within 5 % of its true value and in accordance with ASHRAE Guide 22 and AHRI Standard 550/590. The following instrumentation and installation are also required to be complied with :
Location and installation of the measuring devices to meet the manufacturer’s recommendation. Data acquisition system with a minimum resolution of 16 bit. All data logging with capability to trend at 1 minute sampling time interval. Flow meters are to be provided for chilled-water and condenser water loop and shall be of ultrasonic / full bore magnetic type or equivalent. Temperature sensors are to be provided for chilled water and condenser water loop and shall have an end-to-end measurement uncertainty not exceeding ± 0.05 °C over the entire measurement or calibration range. All thermo-wells shall be installed in a manner that ensures that the sensors can be in direct contact with fluid flow. Provisions shall be made for each temperature measurement location to have two spare thermo-wells located at both side of the temperature sensor for verification of measurement accuracy. Dedicated power meters are to be provided for each of the following groups of equipment : chillers, chilled water pumps, condenser water pumps and cooling towers.
Note : No requirement on VRF system under Current Code | NRB04 NRB 04-1 NRB 04-1 – cont’d NRB04-2 | Measurement and Verification (M & V) Instrumentation Instrumentation for Chilled Water Air-Conditioning System Provision of permanent measuring instruments for monitoring of the energy performance of the chilled water plants and air distribution systems. The installed instrumentation must have the capability to calculate the resultant system efficiency within 5% of its true value in accordance with SS 591. Each measurement system shall include sensors, any signal conditioning, data acquisition system and the wiring connecting these components. The permanent measuring instruments and devices are to be accessible and must not be located directly above the chillers, to facilitate verification and maintenance. They must be installed in accordance with the manufacturers’ recommendation and SS 591. The measurement systems provided shall also comply with the following requirement: All data logging with capability to trend at 1-minute sampling time interval, and recorded to the 3rd decimal digit; Building management system (BMS), standalone energy monitoring system (EMS) or local sequential controller (LSC) shall have capability to compute and display of key indicators including total system energy efficiency and its component (water-side and air-side efficiency) as well as the calculated heat balance of the chilled water system. Magnetic in-line flow meter, with 1% uncertainty and capable of electronic in-situ verification to within ±2% of its original factory calibration. If installation of magnetic in-line meters is not possible, ultrasonic flow meters or other flow meters that can meet the indicated performance may be used; Temperature sensors are to be provided for chilled water and condenser water loop and shall have a measurement uncertainly within ±0.05°C over the entire measurement range. Each temperature measurement location shall have test plugs or additional thermowells located before and after each temperature sensor along the chilled water and condenser water lines for verification of measurement accuracy. All thermo-wells shall be installed in a manner that enables the sensors to be in direct contact with fluid flow; and Dedicated power meters (of IEC Class 1 or better) and metering current transformers (of Class 1 or better) where applicable, are to be provided for each of the following groups of equipment where applicable: chillers, chilled water pumps, condenser water pumps, cooling towers, air distribution sub-system (i.e. AHUs, PAHUs, FCUs).
Note (1) : This requirement Is extended to cover air-cooled chilled water plant Note (2) : Added requirements on the manner and location of the permanent instruments and devices as well as the functionality and capability of data loggers and energy monitoring system for better monitoring as highlighted in blue. Note (3) : Provision of calibrated magnetic in-line flow meters for better measurement accuracy is preferred. Note (4) : It is a new requirement to have dedicated power meters to be provided for air-distribution sub-systems (that is AHUs, PAHUs, FCUs). In the case of FCUs, if submetering cannot be provided, the evidences of way of nameplate motors can be considered. Instrumentation for Variable Refrigerant Flow (VRF) system Provision of permanent measuring instruments for monitoring of the energy performance of the Variable Refrigerant Flow (VRF) condensing units and air distribution systems. The installed instrumentation must have the capability to calculate the resultant system efficiency within 10% uncertainty. Each measurement system shall include sensors, any signal conditioning, data acquisition system and the wiring connecting these components. The measurement systems provided shall also comply with the following requirement: All data logging with capability to trend at 5-minute sampling time interval, and preferably recorded to the 3rd decimal digit; Building management system (BMS), standalone energy monitoring system (EMS) shall have capability to compute and display of the overall system energy efficiency and to facilitate data extraction for verification purpose; and Dedicated power meters (of IEC Class 1 or better) and metering current transformers (of Class 1 or better) where applicable, are to be provided for all condensing units of the VRF system and air distribution sub-systems (i.e. AHUs, PAHUs, FCUs).
Note : This is a new requirement to cover instrumentation for VRF system for better energy monitoring. It is only applicable if the VRF system serve an aggregate conditioned floor areas of 2000 m2 or more. Requirement for dedicated power meters to be provided for air distribution sub-systems (that is AHUs, PAHUs, FCUs). In the case of FCUs, if submetering cannot be provided, the evidences of way of nameplate motors can be considered. Suppliers’ proprietary system can be used to determine the system efficiency of the condensing units.
|
| Note : No requirement on service clearances under Current Code | NRB06 | Maintenance of Building Cooling System Performance Ensure adequate service clearances so that the building cooling system performance can be maintained during operation as designed. Service clearances are to be provided as per manufacturers’ specification or prescribed standards stated in the following clauses, whichever governs. This is applicable to Chillers, Pump Systems, Cooling Towers, Air-Distribution System – AHUs only Note : This is a new requirement to ensure that the building cooling system performance can be maintained during building operation. |
Part 1 – Energy Efficiency | Part 2 – Elective Options under Section 1 : Sustainable Design Strategies |
NRB 1-5 | Daylighting Encourage design that optimises the use of effective daylighting to reduce energy use for artificial lighting. Use of daylight and glare simulation analysis to verify the adequacy of ambient lighting levels in all dwelling unit’s living and dining areas. The ambient lighting levels should meet the illuminance level and Unified Glare Rating (UGR) stated in SS CP 38 – Code of Practice for Artificial lighting in Buildings. Daylighting in the following common areas
Staircases Corridors Lift lobbies Atriums Car parks
Extent of coverage : 80% - with integration with daylight control | NRBE01-3 | Effective Daylighting Normally Occupied Spaces : Daylighting provision with desired lighting level and specific Daylight Autonomy (DA) requirements as outlined in the following table for a minimum 15% of total occupied areas with integration of daylighting controls. S/N | Minimum Lighting Level Based on Space Occupancy Type | Daylight Autonomy requirement per unit area of space |
|---|
1 | Offices and Institutional spaces where lux requirement is 500 lux | DA500lx, 50% | 2 | Industrial, sports facilities, retail areas where lux requirement is 300 lux | DA300lx, 50% | 3 | Hotel, resort-like and service apartment where lux requirement is 200 lux | DA200lx, 50% |
Note : Daylight availability tables will be made available for use to simplify the compliance with daylighting requirement. Daylight simulation is not required.
Common areas : Daylighting provision with integrated daylight controls for minimum coverage of 80% in at least two(2) of the following areas
Lift lobbies Corridors Staircases Car parks Atriums Toilets
|
Part 3 – Environmental Protection | Part 2 – Elective Options – Section 2: Sustainable Construction |
NRB 3-1 | Sustainable Construction Concrete Usage Index (CUI) Encourage designs with efficient use of concrete for building components – Points accorded for a range of CUI from 0.7 to 0.35
| NRBE02-1 | Resource Efficiency Measures Existing building structures with more than 50% of the floor and/or wall areas conserved for adaptive reuse. Design with Concrete Usage Index (CUI) of not more than 0.48. Embodied carbon reporting to account for the upfront carbon emissions of three (3) key construction materials namely, concrete, steel, and glass used in building developments.
Note: Item (a) is similar to the requirement under Green Features and Innovation of Current Code. Item (b) – the methodology will be the same as current Code with a low CUI stipulated to encourage efficient concrete usage Item (c) – A new requirement incorporated to encourage carbon accounting for three key construction materials
|
| Use of Sustainable and Recycled Materials
Green Cements with approved industrial by-product (such as Ground Granulated Blastfurnace Slag (GGBS), silica fume, fly ash) to replace Ordinary Portland Cement (OPC) by at least 10% by mass for superstructural works. Recycled Concrete Aggregates (RCA) and Washed Copper Slag (WCS) from approved sources to replace coarse and fine aggregates for concrete production of main building elements
| NRBE02-2 | Low Carbon Concrete Enhance carbon reduction with the use of following sustainable materials in building construction. Use of concrete with eco-friendly cementitious materials that are classified under CEM II to V types for at least 80% of the super structural works by volume. Use of recycled concrete aggregate (RCA) and/or washed copper slag (WCS) from approved sources that meet the minimum usage requirement (that is 1.5% x GFA for RCA and/or 0.75 x GFA for WCS) Alternative construction materials that can be used as a replacement for standard building materials for non-structural application.
Note : These requirements are generally similar to current Code but are enhanced with stipulated standard and have included new materials for construction such as granite fines. |
NRB 3-2 | Sustainable Products Promote the use of environmentally friendly products that are certified by approved local certification body. Points accorded based on weightage and extent of coverage. Applicable for building products | NRBE02-3 | Sustainable Products Encourage the specification and use of environmentally friendly products that are certified with Environmental Product Declaration (EPD) requirements or two-ticks rating by an approved local certification body. The provision shall include at least three (3) products for 80% of applicable areas or building components. Applicable for building products, M & E products Note : This requirement is enhanced to encourage the use of building products with lower embodied carbon. |
Part 1 – Energy Efficiency | Part 2 – Elective Options – Section 3: Sustainable Technologies |
NRB1 11 | Renewable Energy Encourage the use of renewable energy sources – Points can be accorded based on the % replacement of building electricity consumption. | NRB03-1 | Renewable Energy System Encourage the use of on-site renewable energy sources to reduce the use of electricity by |
| Note : No requirement under Current Code | NRB03-2 | Smart Building Solutions Minimum two (2) building solutions which facilitates some form of automation and controls over building systems for better energy management and thermal comfort as listed below. Use of BACnet, Modbus or any other open protocol as the network backbone of the building management system where data points can be used to facilitate communication and integration with other building systems. Energy portal and dashboard that help building owners and/or tenants to better manage their energy consumption in an intuitive manner. It should comprise display metered data, trending of energy consumption (historical data) on monthly basis of tenants/spaces within buildings and relevant parameters. Real time remote monitoring of chiller plant system performance and operation such as BCA Chiller Efficiency Smart Portal Demand controlled ventilation system such as carbon dioxide sensors or devices to regulate the fresh air intake and ventilation based on occupants’ need. Timer sensors/controls for lighting and/or ventilation systems in common areas and facilities. Smart building sensors that are equipped with sensing capability, microprocessors and communication technology that can help facilitate some form of monitoring or automation. Differential pressure switches for Air Handling Units (AHUs) that are linked to a building management system (BMS) or suitable means that can monitor the air filter condition. Others (to be evaluated on a case to case basis)
|
| Note : No requirement under Current Code | NRB03-3 | Green Building Technologies Low-carbon solutions and technologies which help reduce energy consumption. Examples of solutions that can be considered are as follows : Energy recovery systems for building applications Lifts with regenerative function Passive Displacement ventilation system Dedicated outdoor air system Others (to be evaluated on a case-to-case basis)
Note : Some criteria under Part 5 – Green Features and Innovation under current Code are incorporated. New requirements are included to encourage the use of smart technologies and solutions to minimise building energy consumption. |