NEWater, where available, is supplied to commercial and industrial premises for non-potable uses, such as in cooling towers and suitable process uses, general washing, irrigation, etc.
All new non-domestic developments (eg commercial, industrial, etc) are required to provide a dedicated NEWater pipe system to take in NEWater for non-potable uses when NEWater becomes available in future. This requirement also applies to all existing non-domestic premises undergoing addition / alteration works.
NEWater shall not be used as primary source of water supply for firefighting.
For the above-mentioned proposals, provisions shall be made to receive PUB water as alternate source to NEWater in the event of an interruption due to urgent repairs, construction of new works, alteration to or maintenance of existing works. Examples of these include the provision of a spool piece with double check valves to facilitate switching over from NEWater to PUB water or via dual feed pipes supplying PUB water, through an air gap, and NEWater to the NEWater break tank. There shall be no cross-connection between the PUB water and NEWater supply pipes. For development proposals with the provision of NEWater submeter, there shall be no spool piece arrangement at the master meters for the purpose of providing alternate supply using PUB water.